9 - DIAGNOSTICS
Code
Description
Possible cause
Action taken on the unit
Reset type
4703
Loss of communication with VFD Pump
Drive Board Number 1
Bus installation fault,
communication error
Unit is stopped and restarted with
the second pump (if available); If
there is no pump available, the
unit shuts down
Automatic, if communication is
re-established
4704
Loss of communication with VFD Pump
Drive Board Number 2
Bus installation fault,
communication error
Unit is stopped and restarted with
the second pump (if available); If
there is no pump available, the
unit shuts down
Automatic, if communication is
re-established
PROCESS FAILURES
10001
Water Exchanger Freeze Protection
No water flow, defective
thermistor
Unit shuts down but the pump
continues to run
Automatic (the first alarm in the last
24h); otherwise, Manual
10005
Circuit A Low Saturated Suction
Temperature
Pressure transducer defective,
EXV blocked or lack of refrigerant
Circuit A shuts down
Automatic (the first alarm in the last
24h); otherwise, Manual
10006
Circuit B Low Saturated Suction
Temperature
Pressure transducer defective,
EXV blocked or lack of refrigerant
Circuit B shuts down
Automatic (the first alarm in the last
24h); otherwise, Manual
10008
Circuit A High Superheat
Pressure transducer defective,
temperature sensor defective,
EXV blocked or lack of refrigerant
Circuit A shuts down
Manual
10009
Circuit B High Superheat
Pressure transducer defective,
temperature sensor defective,
EXV blocked or lack of refrigerant
Circuit B shuts down
Manual
10011
Circuit A Low Superheat
Pressure transducer defective,
temperature sensor defective,
EXV blocked or lack of refrigerant
Circuit A shuts down
Manual
10012
Circuit B Low Superheat
Pressure transducer defective,
temperature sensor defective,
EXV blocked or lack of refrigerant
Circuit B shuts down
Manual
10014
Customer Interlock Failure
Customer interlock input set "On"
Unit shuts down
Automatic (if the unit was stopped);
otherwise, Manual
10016
Compressor A1 Not Started or Pressure
Increase not established
Compressor breaker or fuse fault,
compressor switch open
Compressor A1 shuts down
Manual
10017
Compressor A2 Not Started or Pressure
Increase not established
Compressor breaker or fuse fault,
compressor switch open
Compressor A2 shuts down
Manual
10018
Compressor A3 Not Started or Pressure
Increase not established
Compressor breaker or fuse fault,
compressor switch open
Compressor A3 shuts down
Manual
10019
Compressor A4 Not Started or Pressure
Increase not established
Compressor breaker or fuse fault,
compressor switch open
Compressor A4 shuts down
Manual
10020
Compressor B1 Not Started or
Pressure Increase not established
Compressor breaker or fuse fault,
compressor switch open
Compressor B1 shuts down
Manual
10021
Compressor B2 Not Started or
Pressure Increase not established
Compressor breaker or fuse fault,
compressor switch open
Compressor B2 shuts down
Manual
10022
Compressor B3 Not Started or
Pressure Increase not established
Compressor breaker or fuse fault,
compressor switch open
Compressor B3 shuts down
Manual
10023
Compressor B4 Not Started or
Pressure Increase not established
Compressor breaker or fuse fault,
compressor switch open
Compressor B4 shuts down
Manual
10028
Main Power Supply Fault
Power supply fault, high
temperature in the electrical box
Unit shuts down and it is not
allowed to start
Automatic, if the input is closed
10030
Master/Slave Communication Failure
Bus installation fault
Master/Slave control is stopped
/ Unit returns to the stand-alone
mode
Automatic, if communication is
restored
10031
Unit is in Network emergency stop
Network emergency stop
command
Unit shuts down
Automatic, if emergency stop is
deactivated
10032
Water Pump #1 fault
Flow switch or water pump fault
Unit is restarted with another
pump running; If no pump is
available, the unit shuts down
Manual
10033
Water Pump #2 fault
Flow switch or water pump fault
Unit is restarted with another
pump running; If no pump is
available, the unit shuts down
Manual
10037
Circuit A - Repeated High Discharge
Gas Overrides
Repetitive capacity decreases
None OR circuit A shuts down
Automatic (no discharge gas
overrides within 30 min) or Manual
10038
Circuit B - Repeated High Discharge
Gas Overrides
Repetitive capacity decreases
None OR circuit B shuts down
Automatic (no discharge gas
overrides within 30 min) or Manual
10040
Circuit A - Repeated Low Suction Temp
Overrides
Repetitive capacity decreases
Circuit A shuts down
Manual
10041
Circuit B - Repeated Low Suction Temp
Overrides
Repetitive capacity decreases
Circuit B shuts down
Manual
AQUACIAT
POWER
EN-50