Pressures Menu – PRESSURE
Name
Status
Default
Unit
Displayed text*
Description
1
DP_A
-
-
kPa / PSI
Discharge Pressure A
Compressor discharge pressure, circuit A
2
SP_A
-
-
kPa / PSI
Main Suction Pressure A
Compressor suction pressure, circuit A
3
DP_B
-
-
kPa / PSI
Discharge Pressure B
Compressor discharge pressure, circuit B
4
SP_B
-
-
kPa / PSI
Main Suction Pressure B
Compressor suction pressure, circuit B
5
PUMP_EWP
-
-
kPa / PSI
Inlet unit water pres.
Pump entering water pressure
6
PUMP_LWP
-
-
kPa / PSI
Outlet unit water pres.
Pump leaving water pressure
* Depends on the selected language (French by default).
Inputs Menu – INPUTS
Point name
Status
Default
Unit
Displayed text*
Description
1
ONOFF_SW
open/close
open
-
Remote On/Off Switch
Remote on/off switch
2
HC_SW
open/close
open
-
Remote HeatCool Switch
Remote heating/cooling selection switch
3
SETP_SW
open/close
open
-
Remote Setpoint Switch
Remote setpoint selection switch
4
LIM_SW1
open/close
open
-
Limit Switch 1
Demand limit switch 1
5
LIM_SW2
open/close
open
-
Limit Switch 2
Demand limit switch 2 (Energy Management Module)
6
LOCK_SW
open/close
open
-
Customer Interlock
Customer interlock: When the contact is closed, the unit will be stopped
with no delay. The switch is provided on the customer's terminal block
of the optional Energy Management Module
7
FLOW_SW
open/close
open
-
Flow Switch Status
Flow switch status
8
DSHTR_SW
open/close
open
-
Desuper heater demand
Desuperheater status
9
REM_LOCK
open/close
open
-
Remote Interlock Status
Remote interlock status
10
REVPH_SW
open/close
open
-
Reverse Phase Detection Reverse phase detection
11
cp_a1_f
open/close
open
-
Compressor A1 failure
Compressor A1 failure
12
cp_a2_f
open/close
open
-
Compressor A2 failure
Compressor A2 failure
13
cp_a3_f
open/close
open
-
Compressor A3 failure
Compressor A3 failure
14
cp_a4_f
open/close
open
-
Compressor A4 failure
Compressor A4 failure
15
HP_SW_A
open/close
open
-
High Pressure Switch A
High pressure switch, circuit A
16
LEAK_A
-
-
V
Leakage Detector Val A
Leakage detector, circuit A
17
cp_b1_f
open/close
open
-
Compressor B1 failure
Compressor B1 failure
18
cp_b2_f
open/close
open
-
Compressor B2 failure
Compressor B2 failure
19
cp_b3_f
open/close
open
-
Compressor B3 failure
Compressor B3 failure
20
cp_b4_f
open/close
open
-
Compressor B4 failure
Compressor B4 failure
21
HP_SW_B
open/close
open
-
High Pressure Switch B
High pressure switch, circuit B
23
LEAK_B
-
-
V
Leakage Detector Val B
Leakage detector, circuit B
* Depends on the selected language (French by default).
Outputs Menu – OUTPUTS
Point name
Status
Default
Unit
Displayed text*
Description
1
CP_A1
off/on
off
-
Compressor A1
Compressor A1 command
2
CP_A2
off/on
off
-
Compressor A2
Compressor A2 command
3
CP_A3
off/on
off
-
Compressor A3
Compressor A3 command
4
CP_A4
off/on
off
-
Compressor A4
Compressor A4 command
5
FAN_A1_0
off/on
off
-
Fan A1 Low Speed
Fan A1 low speed (optional)
6
FAN_A1_1
off/on
off
-
Fan A1 High Speed
Fan A1 command
7
FAN_A2
off/on
off
-
Fan A2
Fan A2 command
8
FAN_A3
off/on
off
-
Fan A3
Fan A3 command
9
FAN_A4
off/on
off
-
Fan A4
Fan A4 command
10
FAN_ST_A
0 to 6
0
-
Fan Staging Number Cir A Current fan stage of circuit A
11
VARFAN_A
0 to 100
0
%
Variable fan A command
Variable fan A command
12
EXV_A
0 to 100
0
%
EXV position Circuit A
EXV position, circuit A
13
REV_A
off/on
off
-
4-way Refrig. Valve A
4-way refrigerant valve, circuit A: Used to manage cooling / heating /
defrost operation (heat pumps)
14
HD_HTR_A
off/on
off
-
Compressor Head Heater A Compressor head heater, circuit A (only units with variable speed fans
controlled through the internal bus)
7 - CONNECT TOUCH CONTROL: MENU STRUCTURE
AQUACIAT
POWER
EN-24