12.2.5 - TOTAL HEAT RECOVERY
The AQUACIAT
POWER™
range can be equipped with a total heat recovery function as an option
The principle consists of producing free additional hot water at a high temperature of up to 65°C by adding a dual-circuit water-cooled
condenser which allows all the heat released by the machine to be recovered.
This optional configuration requires assembly in our factories and is by order only.
Operating principle
If hot water production is required, the compressor discharge gases are directed towards the heat recovery condenser. The refrigerant
releases its heat to the hot water that leaves the condenser at a temperature of up to 60°C. In this way, 100% of the heat rejected by the
liquid chiller can be used to produce hot water. When the demand for heat is satisfied, the hot gas is again directed towards the air
condenser where the heat is rejected to the outside air by the fans.
Hot water temperature control is ensured by the machine's Connect Touch control that independently controls the recovery operation
of each refrigerant circuit.
Note: Heat recovery is only possible if the machine produces cold water at the same time.
12.2.5.1 - Physical properties of units with total heat recovery
AQUACIAT
POWER™
LD
0602R 0650R 0750R 0900R 1100R 1200R 1350R 1400R 1600R 1750R
Total recovery exchanger
Brazed-plate heat exchanger
Water volume circuits A/B
l
20
24
24
29
29
31
31
31
31
44
Maximum operating pressure, water side
kPa
600
600
600
600
600
600
600
600
600
600
Hydraulic connections
Victaulic
Connection
in
3"
3"
3"
3"
3"
4"
4"
4"
4"
4"
External diameter
mm
88,9
88,9
88,9
88,9
88,9
114,3
114,3
114,3
114,3
114,3
Operating weight
(1)
Standard unit + total recovery
kg
1490
1580
1580
1740
1775
2300
2354
4561
2620
3084
Unit + Ultra Low Noise + total recovery option
kg
1573
1663
1663
1849
1884
2427
2481
4706
2765
3247
Refrigerant
(2)
R32 / A2L / GWP=675 as per AR4
Circuit A
kg
11,8
14,1
14,1
19,8
20,2
20,6
21,4
29,5
30,2
30,6
tCO
2
e
8,0
9,5
9,5
13,4
13,6
13,9
14,4
19,9
20,4
20,7
Circuit B
kg
16,7
19,7
19,7
19,8
20,2
28,9
29,7
29,5
30,2
35,2
tCO
2
e
11,3
13,3
13,3
13,4
13,6
19,5
20,0
19,9
20,4
23,8
AQUACIAT
POWER™
LD
1800R 2000R 2200R 2400R 2650R 2800R 2950R 3200R 3500R
Total recovery exchanger
Brazed-plate heat exchanger
Water volume circuits A/B
l
44
44
61
61
61
61
61
61
61
Maximum operating pressure, water side
kPa
600
600
600
600
600
600
600
600
600
Hydraulic connections
Victaulic
Connection
in
4"
4"
5"
5"
5"
5"
5"
5"
5"
External diameter
mm
114,3
114,3
139,7
139,7
139,7
139,7
139,7
139,7
139,7
Operating weight
(1)
Standard unit + total recovery
kg
3110
3315
3848
4093
4093
4627
4627
4876
4876
Unit + Ultra Low Noise + total recovery option
kg
3273
3496
3981
4246
4246
4801
4801
5070
5070
Refrigerant
(2)
R32 / A2L / GWP=675 as per AR4
Circuit A
kg
30,9
36,1
44
45,5
45,5
47,2
47,2
53,8
53,8
tCO
2
e
20,9
24,4
29,7
30,7
30,7
31,9
31,9
36,3
36,3
Circuit B
kg
35,6
36,1
45,5
45,5
45,5
53,8
53,8
53,8
53,8
tCO
2
e
24,0
24,4
30,7
30,7
30,7
36,3
36,3
36,3
36,3
(1) Weights are guidelines only. Refer to the unit name plate.
(2) Values are guidelines only. Refer to the unit name plate.