12.2.8 - Units with available pressure fans
The design of this range using R32, is intended for outdoor
installation. Machine installation indoors is forbidden. Units with
fans with available pressure are designed to be ducted to the fan
discharge which results in pressure drops in the air circuit.
It is for this reason that more powerful fan motors are installed for
this option.
For each installation, the duct pressure drops differ, depending
on the duct length, the duct section and the changes in direction.
Ductable units equipped with this option are designed to operate
with ducts whose air evacuation generates a maximum pressure
drop of 200 Pa.
Using a speed variation up to 19 rps enables the system to
overcome the pressure drops in the ducts while maintaining an
optimised air flow in each circuit.
All the fans in the same circuit run at the same time at the same
speed.
In the cooling/heating mode, the full load or partial load speed is
controlled by a patented algorithm that permanently optimizes the
condensation/evaporation temperature to ensure the best unit
energy efficiency (EER/COP) whatever the operating conditions
and pressure drop of the duct network.
If required by a specific installation, the unit's maximum fan speed
can be configured in the Service Configuration menu. Refer to the
control manual.
The maximum configured speed applies to both the cooling and
heating modes.
The performances (capacity, efficiency, noise level) depend on
the fan speed and the duct network. Please refer to the
manufacturer's electronic catalogue to evaluate the estimated
impact of the ducting system on the unit's operating conditions.
12.2.8.1 -
Specific installation in ductable units
The rotation speed of all the fans in the same circuit is controlled
in the same way.
Therefore each circuit operates independently.
Each refrigerant circuit must have an independent network of ducts
to prevent any recycling of air between the air-cooled exchangers
of different refrigerant circuits.
On ductable units, each fan is equipped with a factory-fitted
connection interface frame providing a link between the duct
network itself and the refrigerant circuit to which the fan belongs.
Refer to the dimensional plans of the units for the precise
dimensions of this connection interface.
Please refer to the chapter ‘‘Arrangement of fans’’ to assign each
fan to their own circuit.
Specific instructions for AQUACIAT
POWER™
ILD
When the ILD units operate in heating mode,
dehumidification of the air and defrosting of the
air-cooled exchangers generate a large amount of
condensate that must be evacuated from the
installation site.
The ILD units must be installed on a waterproof base
enabling efficient drainage and evacuation of the
condensate from the exchangers.
At low ambient temperature, when the exchangers
form frost, the defrost water must be collected to
ensure that there is no risk of flooding of the area
where the units are installed.
12.2.8.2 -
Nominal and maximum air flow rate per circuit
and per unit type
AQUACIAT
POWER™
LD
Rated air flow
rate
(1)
(l/s)
Maximum air flow
rate
(2)
(l/s)
602R
13500
20160
650R
18220
26880
750R
18110
26880
900R
18010
26880
1100R
17770
26880
1200R
22370
33600
1350R
22180
33600
1400R
26810
40320
1600R
26610
40320
1750R
31230
47040
1800R
31050
47040
2000R
35490
53760
2200R
39990
60480
2400R
44470
67200
2650R
44200
67200
2800R
48710
73920
2950R
48570
73920
3200R
52970
80640
3500R
52620
80640
AQUACIAT
POWER™
ILD
Rated air flow
rate
(1)
(l/s)
Maximum air flow
rate
(2)
(l/s)
602R
14010
18720
700R
13920
18720
800R
18700
24960
900R
18590
24960
1000R
18490
24960
1150R
23200
31200
1250R
23080
31200
1400R
27840
37440
1500R
27700
37440
1600R
32480
43680
1750R
32320
43680
2000R
36980
49920
(1) The rated air flow rate is set in accordance with Eurovent 12/7 - 35°C, with an
operating pressure of 160 Pa.
(2) The maximum air flow rate corresponds to the maximum obtainable by these
fans (maximum speed, operating pressure = 0 Pa)
These values are given for illustrative purposes only. The actual and up-to-date
flow rates based on the condition are indicated via the selection on the electronic
catalogue.
12.2.8.3 - Air connection on discharge
Refer to the dimensional plans of the units for the precise
dimensions of the connection interface.
A flexible sleeve providing connection to the duct network is
delivered with the unit.