11.4 - Fans
Each fan motor assembly is equipped with a high-performance impeller made from recyclable composite material.
The motors are three-phase, with lifetime lubricated bearings and class F insulation (IP55 level).
When the XtraFan option is not selected, the pressure available at the fan outlet is zero.
According to regulation No. 327/2011 implementing directive 2009/125/EC with regard to ecodesign requirements for fans
driven by motors with an electric input power between 125 W and 500 kW.
Product
AQUACIAT
POWER™
LD 602R-3500R
Options
Options:
High performance
Nominal or
Extended
application range
(high speed)
AQUACIAT
POWER™
LD standard
version up to
size 1400R
VLN/ULN acoustic
version
(Low speed)
AQUACIAT
POWER™
LD
Standard version
from size 1600R
Options: High
seasonal
performance or
All-season operation
(VSD)
High seasonal
efficiency (EC)
XtraFan option
Overall efficiency
38,7
35,3
40,1
47,3
40,0
Measurement category
%
A
A
A
A
A
Efficiency category
Static
Static
Static
Static
Static
Target efficiency level ERP2015
N(2015) 40
N(2015) 40
N(2015) 40
N(2015) 40
N(2015) 40
Efficiency level at the optimum
efficiency point
43,3
42,1
44,6
52,2
43,1
Speed regulator
NO
NO
YES
YES
YES
Year of manufacture
See label on the unit See label on the unit See label on the unit See label on the unit See label on the unit
Fan manufacturer
Simonin
Simonin
Simonin
Simonin
Simonin
Motor manufacturer
Leroy Somer
Leroy Somer
Leroy Somer
EBM
Leroy Somer
Fan PN
00PSG002630700A 00PSG002630700A 00PSG002630700A 00PSG002630700A 00PSG002630700A
Motor PN
00PPG000558400A 00PPG000558500A 00PPG000558700A 00PSG002696800A 00PPG000558600A
Nominal motor capacity
1,90
0,85
1,96
1,68
4,22
Flow rate
kW
4,22
3,10
4,22
4,24
5,31
Pressure at optimum energy
efficiency
m
3
/s
174
97
174
175
216
Nominal speed
Pa
949
710
948
959
1125
Specific ratio
rpm
1,002
1,002
1,002
1,002
1,002
Relevant information to facilitate the
disassembly, recycling or removal of
the product at the end of the life
See the
maintenance manual
See the
maintenance manual
See the
maintenance manual
See the
maintenance manual
See the
maintenance manual
Relevant information to minimise
impact on the environment
See the
maintenance manual
See the
maintenance manual
See the
maintenance manual
See the
maintenance manual
See the
maintenance manual
Regulation 2019/1781 repealing regulation 640/2009 governs the requirements relating to ecodesign applicable to electric
motors and to speed regulators in accordance with directive 2009/125/EC.Our fan motor assemblies are exempt from this.
Product
Options:
High performance
Nominal or
Extended
application range
(high speed)
AQUACIAT
POWER™
LD standard
version up to
size 1400R
VLN/ULN acoustic
version
(Low speed)
AQUACIAT
POWER™
LD
Basic version from
size 1600R
Options: Seasonal
high performance or
all-season operation
(VSD )
High seasonal
efficiency (EC)
XtraFan option
Motor type
Asynchronous
Asynchronous
Asynchronous
Synchronous
Asynchronous
Number of poles
6
8
6
-
6
Nominal input frequency
Hz
50
50
50
50
60
Nominal voltage
V
400
400
400
400
400
Number of phases
3
3
3
3
3
Motor included in the scope
of application of regulation
2019/1781
NO
NO
NO
NO
NO
Justification for exemption
Article 2.1
Article 2.1
Article 2.1
Article 2.1
Article 2.1
Ambient air temperature for
which the motor is specifically
designed
°C
70
70
701
70
70
The above data for fans and motors, are mandatory as part of ecodesign regulations, and are provided for a standalone component
(not included in the cooling system).
11 - MAIN COMPONENTS OF THE UNIT AND OPERATING CHARACTERISTICS
AQUACIAT
POWER
™ LD/ILD
EN-48