Table of minimum and maximum cable sections (per phase) for connection to the units
AQUACIAT
POWER™
LD
Max. connectable section
(1)
Calculation of favourable case:
No. 13 Perforated horizontal raceway or
no. 17 self-supporting cable - PR (90°C) - 45°C
Calculation of unfavourable case:
No. 41 Closed conduit - PR (90°C) - 45°C
Tightening
torque
Connection
hole
Recommended
max. lug width
Section
(2)
Max. length for
a voltage drop
< 5%
Cable type
(3)
Section
(2)
Max. length for
a voltage drop
< 5%
Cable type
(3)
Nm
mm
qty x mm²
(per phase)
m
-
qty x mm²
(per phase)
m
-
Standard unit
0602R
15
M8
25
1x50
180
90°C
2x25
190
90°C or 70°C
0650R
15
M8
25
1x50
180
90°C
2x35
210
90°C or 70°C
0750R
15
M8
25
1x70
190
90°C
2x35
210
90°C or 70°C
0900R
15
M8
25
1x70
190
90°C
2x50
240
90°C or 70°C
1100R
15
M8
25
2x35
170
90°C
2x70
260
90°C or 70°C
1200R
50
M10
32
2x50
190
90°C
2x70
260
90°C or 70°C
1350R
50
M10
32
2x50
190
90°C
2x70
260
90°C or 70°C
1400R
50
M10
32
2x70
200
90°C
2x95
270
90°C or 70°C
1600R
50
M10
32
2x70
200
90°C
2x95
270
90°C or 70°C
1750R
50
M10
32
2x70
200
90°C
2x120
290
90°C or 70°C
1800R
50
M10
32
2x95
210
90°C
2x120
290
90°C or 70°C
2000R
50
M10
32
2x95
210
90°C
2x150
300
90°C or 70°C
2200R
50
M10
32
2x120
220
90°C
2x185
310
90°C or 70°C
2400R
50
M10
32
2x150
220
90°C
2x240
320
90°C or 70°C
2650R
50
M10
32
2x150
230
90°C
2x240
320
90°C or 70°C
2800R
50
M10
32
2x185
240
90°C
4x120
300
90°C or 70°C
2950R
50
M10
32
2x185
240
90°C
4x150
310
90°C or 70°C
3200R
50
M10
32
2x240
240
90°C
4x150
310
90°C or 70°C
3500R
50
M10
32
2x240
240
90°C
4x185
300
90°C or 70°C
AQUACIAT
POWER™
ILD
Max. connectable section
(1)
Calculation of favourable case:
No. 13 Perforated horizontal raceway or
no. 17 self-supporting cable - PR (90°C) - 45°C
Calculation of unfavourable case:
No. 41 Closed conduit - PR (90°C) - 45°C
Tightening
torque
Connection
hole
Recommended
max. lug width
Section
(2)
Max. length for
a voltage drop
< 5%
Cable type
(3)
Section
(2)
Max. length for
a voltage drop
< 5%
Cable type
(3)
Nm
mm
qty x mm²
(per phase)
m
-
qty x mm²
(per phase)
m
-
Standard unit
0602R
15
M8
25
1x50
180
90°C
2x25
190
90°C or 70°C
0700R
15
M8
25
1x50
180
90°C
2x35
210
90°C or 70°C
0800R
15
M8
25
1x70
190
90°C
2x35
210
90°C or 70°C
0900R
15
M8
25
1x70
190
90°C
2x50
240
90°C or 70°C
1000R
15
M8
25
2x35
170
90°C
2x70
260
90°C or 70°C
1150R
50
M10
32
2x50
190
90°C
2x70
260
90°C or 70°C
1250R
50
M10
32
2x50
190
90°C
2x70
260
90°C or 70°C
1400R
50
M10
32
2x70
200
90°C
2x95
270
90°C or 70°C
1500R
50
M10
32
2x70
200
90°C
2x95
270
90°C or 70°C
1600R
50
M10
32
2x70
200
90°C
2x120
290
90°C or 70°C
1750R
50
M10
32
2x95
210
90°C
2x120
290
90°C or 70°C
2000R
50
M10
32
2x95
210
90°C
2x150
300
90°C or 70°C
(1) Connection capacities actually available for each machine. These are defined according to the connection terminal size, the electrical box access opening dimensions,
and the available space inside the electrical box.
(2) Selection simulation result considering the hypotheses indicated.
(3) If the maximum calculated selection is for a 90°C cable type, this means that a selection based on a 70°C cable type can exceed the connection capacity actually
available. Special attention must be given to selection.
The protection against direct contact at the electrical connection point is compatible with the addition of fanout cables. The installer must determine whether these are
necessary based on the cable sizing calculation.
Note:
The currents considered are given for a machine fitted with a hydraulic module operating at the maximum current.
6 - ELECTRICAL CONNECTION