4.3 - Free spaces
The free spaces presented are determined in order to ensure
sufficient working and manoeuvring space to carry out maintenance
operations on the unit in suitable ergonomic conditions
Key:
All dimensions are given in mm.
B
Clearances required for maintenance and air flow
C
Clearance recommended for coil removal
4.4 - Positioning of ATEX zones around the unit
Electrical cabinet side
Due to the nature of the refrigerant in these units (A2L fluid),
ATEX zones have been identified and positioned around the units,
as shown in the diagram opposite.
The ATEX zones, as defined, must only be entered by suitably
trained personnel equipped with the appropriate detection
material and tools for working in an ATEX zone.
ATEX zone 2 is involved.
The machines are designed to be installed outdoors, in a free
field-type, ventilated area.
As the refrigerant used is heavier than air, it is essential that
installations joined to the unit prevent the retention of refrigerant
at the lowest point in the event of a leak.
4.5 - Installing several units
It is recommended to install multiple units in a single row, arranged
as shown in the example below, to avoid recycling air between
the units. If the floor space does not allow this arrangement, contact
your distributor to assess the various installation options.
1500 mm min.
1500 mm min.
4.6 - Distance to the wall
Anti-vibration
mounts
To guarantee correct operation in most cases:
If h < H, S minimum = 3 m
If h > H or S < 3 m, contact your distributor to assess the various
installation options.
4 - DIMENSIONS, CLEARANCES, MINIMUM INSTALLATION DISTANCES
AQUACIAT
POWER
™ LD/ILD
EN-8