12 - OPTIONS
12.2.5 - Power factor correction
The power factor correction is active for all of the machine's operating conditions.
A power factor performance of 0.95 is guaranteed when the unit is running in conditions which require a power supply that exceeds
the Eurovent standard condition.
A capacitor battery is controlled by a controller which reads the current draw by the unit and adjusts the power factor to a setting
of 0.95.
Capacitors are dry type : no risk of leakage or fire.
The capacitors are selected for each unit as per below table:
Size of the AQUACIAT
POWER
ILD ST / HE unit
602
650
800
900
902
1000
1150
1200
1400
1600
1800
2000
Capacitors Capacity (kVAR)
30
30
40
40
40
50
50
60
70
80
80
80
Capacitor 1
Capacity (kVAR)
10
10
10
10
10
10
10
20
10
20
20
20
Ir(A)
14
14
14
14
14
14
14
29
14
29
29
29
Capacitor 2
Capacity (kVAR)
20
20
10
10
10
20
20
20
20
20
20
20
Ir(A)
29
29
14
14
14
29
29
29
29
29
29
29
Capacitor 3
Capacity (kVAR)
-
-
20
20
20
20
20
20
40
40
40
40
Ir(A)
-
-
29
29
29
29
29
29
58
58
58
58
Caution: Operation of the unit without capacitors results in an increase in the current.
12.2.6 -
Water filter and flexible connective couplings
Below are the equipment diagrams depending on the different configurations:
Flexible water filter
ILD 602 à 2000
Machine ILD
Legend
B
Victaulic flange coupling
C
Vibration-damping coupling
D
800 µm screen filter
E
Butterfly valve
F
Victaulic clamp
G
GRAPHITE gaskets (PH)
Water outlet
Water inlet
EN-59
AQUACIAT
POWER
ILD