5 - PHYSICAL AND ELECTRICAL DATA FOR THE UNITS
5.1 - Physical characteristics
AQUACIAT
POWER
ILD ST
602
650
800
900
902
1000
1150
1200
1400
1600
1800
2000
Sound levels
Standard unit
Sound power
(1)
dB(A)
90
91
91
91
92
92
93
93
94
94
94
94
Sound pressure at 10 m
(2)
dB(A)
58
59
59
59
60
60
61
61
62
62
62
62
Unit + Low Noise option
Sound power
(1)
dB(A)
89
90
90
90
91
91
91
92
92
93
93
93
Sound pressure at 10 m
(2)
dB(A)
57
58
58
58
59
59
59
60
60
61
61
61
Dimensions
Length
mm
2410
3604
4797
Width
mm
2253
2253
2253
Height
mm
2322
2322
2322
Unit + Buffer tank module option
mm
3604
4798
5991
Operating weight
(3)
Standard unit
kg
1443
1518
1646
1669
2090
2257
2382
2613
3094
3344
3356
3396
Unit + Low Noise option
kg
1514
1585
1739
1762
2179
2383
2508
2757
3256
3524
3536
3576
Unit + Low Noise HP dual-pump
hydraulic module
kg
1704
1748
1913
1936
2398
2630
2763
2998
3538
3806
3855
3894
Unit + Low Noise HP dual-pump
hydraulic Buffer tank module
kg
2652
2692
2857
2880
3338
3589
3722
3957
4497
4765
4814
4853
Compressors
Hermetic Scroll 48.3 rps
Circuit A
1
1
2
2
2
2
2
2
3
4
4
4
Circuit B
2
2
2
2
2
3
3
4
4
4
4
4
No. of control stages
3
3
4
4
4
5
5
6
7
8
8
8
Refrigerant
(3)
R410A
Circuit A
kg
14,5
22,0
23,0
24,0
27,0
27,0
30,0
33,0
42,0
53,0
54,0
56,0
tCO
2
e
30,3
45,9
48,0
50,1
56,4
56,4
62,6
68,9
87,7
110,7
112,8
116,9
Circuit B
kg
23,0
23,0
23,0
24,0
35,0
36,0
48,5
53,0
53,0
53,0
54,0
56,0
tCO
2
e
48,0
48,0
48,0
50,1
73,1
75,2
101,3
110,7
110,7
110,7
112,8
116,9
Oil charge
Circuit A
l
6,9
6,9
13,8
13,8
13,8
13,8
13,8
13,8
20,7
27,6
27,6
27,6
Circuit B
l
13,8
13,8
13,8
13,8
13,8
20,7
20,7
27,6
27,6
27,6
27,6
27,6
Control
Connect Touch Control
Minimum capacity
%
33%
33%
25%
25%
25%
20%
20%
17%
14%
13%
13%
13%
Air-cooled exchanger
Grooved copper tubes and aluminium fins (RTPF)
(1) in dB ref=10
-12
W, 'A' weighted. Declared dual-number noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). Measurements
according to ISO 9614-1 under nominal operating conditions EN14511 - cooling mode.
(2) In dB ref 20µPa, 'A' weighted. Declared dual-number noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). For
information, calculated from the sound power Lw(A).
(3) Values are guidelines only. Refer to the unit nameplate.
Eurovent certified values
EN-15
AQUACIAT
POWER
ILD