5 - PHYSICAL AND ELECTRICAL DATA FOR THE UNITS
AQUACIAT
POWER
ILD HE
602
650
800
900
902
1000
1150
1200
1400
1600
1800
2000
Sound levels
Standard unit
Sound power
(1)
dB(A)
90
91
91
91
92
92
93
93
94
94
94
94
Sound pressure at 10 m
(2)
dB(A)
58
59
59
59
60
60
61
61
62
62
62
62
Unit + Low Noise option
Sound power
(1)
dB(A)
89
90
90
90
91
91
91
92
92
93
93
93
Sound pressure at 10 m
(2)
dB(A)
57
58
58
58
59
59
59
60
60
61
61
61
Unit + Xtra Low Noise option
Sound power
(1)
dB(A)
84
85
86
86
86
87
87
87
88
89
89
89
Sound pressure at 10 m
(2)
dB(A)
52
53
54
54
54
55
55
55
56
57
57
57
Unit + Super Low Noise option
Sound power
(1)
dB(A)
82
83
84
84
84
85
85
86
86
87
87
87
Sound pressure at 10 m
(2)
dB(A)
50
51
52
52
52
53
53
54
54
55
55
55
Dimensions
Length
mm
2410
3604
4797
Width
mm
2253
2253
2253
Height
mm
2322
2322
2322
Unit + Buffer tank module option
mm
3604
4798
5991
Operating weight
(3)
Standard unit
kg
1479
1554
1683
1705
2127
2274
2396
2626
3104
3370
3382
3432
Unit + Low Noise option
kg
1550
1622
1775
1798
2215
2400
2499
2747
3239
3520
3532
3612
Unit + Low Noise HP dual-pump
hydraulic module
kg
1717
1785
1950
2003
2395
2648
2731
3012
3494
3771
3820
3929
Unit + Low Noise HP dual-pump
hydraulic Buffer tank module
kg
2664
2728
2894
2946
3335
3588
3667
3948
4426
4699
4748
4858
Compressors
Hermetic Scroll 48.3 rps
Circuit A
1
1
2
2
2
2
2
2
3
4
4
4
Circuit B
2
2
2
2
2
3
3
4
4
4
4
4
No. of control stages
3
3
4
4
4
5
5
6
7
8
8
8
Refrigerant
(3)
R410A
Circuit A
kg
14,5
22,0
23,0
24,0
27,0
27,0
30,0
33,0
42,0
53,0
54,0
56,0
tCO
2
e
30,3
45,9
48,0
50,1
56,4
56,4
62,6
68,9
87,7
110,7
112,8
116,9
Circuit B
kg
23,0
23,0
23,0
24,0
35,0
36,0
48,5
53,0
53,0
53,0
54,0
56,0
tCO
2
e
48,0
48,0
48,0
50,1
73,1
75,2
101,3
110,7
110,7
110,7
112,8
116,9
Oil charge
Circuit A
l
6,9
6,9
13,8
13,8
13,8
13,8
13,8
13,8
20,7
27,6
27,6
27,6
Circuit B
l
13,8
13,8
13,8
13,8
13,8
20,7
20,7
27,6
27,6
27,6
27,6
27,6
Control
Connect Touch Control
Minimum capacity
%
33%
33%
25%
25%
25%
20%
20%
17%
14%
13%
13%
13%
Air-cooled exchanger
Grooved copper tubes and aluminium fins (RTPF)
(1) in dB ref=10
-12
W, 'A' weighted. Declared dual-number noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)).
Measurements according to ISO 9614-1 under nominal operating conditions EN14511 - cooling mode.
(2) In dB ref 20µPa, 'A' weighted. Declared dual-number noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). For
information, calculated from the sound power Lw(A).
(3) Values are guidelines only. Refer to the unit nameplate.
Eurovent certified values
EN-17
AQUACIAT
POWER
ILD