9.6 - Available static pressure for the installation
Units with hydronic module (fixed speed pump or variable speed pump at 50 Hz)
Data applicable for:
-
Pure water at 20 °C.
-
Refer to the "Water type heat exchanger water flow" section for the maximum water flow values.
-
If ethylene glycol is used, the maximum flow rate is reduced.
If the filter option and/or buffer tank is fitted, the curves below do not take the pressure drops for these components
into account. If necessary, refer to the water filter and/or buffer tank characteristic curves to correct the data
below.
High pressure pumps (Single pumps)
Sizes 602-902
Flow rate, l/s
Pressure head, kPa
B
C D
E
1 AQUACIAT
POWER
ILD ST / HE 602-650
2 AQUACIAT
POWER
ILD ST / HE 800
3 AQUACIAT
POWER
ILD ST / HE 900
4 AQUACIAT
POWER
ILD ST / HE 902
Sizes 1000-2000
Flow rate, l/s
Pressure head, kPa
F G
H
I
5 AQUACIAT
POWER
ILD ST / HE 1000-1150
6 AQUACIAT
POWER
ILD ST / HE 1200-1400
7 AQUACIAT
POWER
ILD ST / HE 1600-1800
8 AQUACIAT
POWER
ILD ST / HE 2000
9 - NOMINAL SYSTEM WATER FLOW CONTROL
EN-39
AQUACIAT
POWER
ILD