Filters
M5 HEE filter:
F7 HEE filter:
F9 HEE filter:
Thickness: 48
Fire rating: M1
Thickness: 48
Fire rating: M1
Thickness: 48
Fire rating: M1
Floway “Classic PHE” and “Classic RHE/RHE-Z” filters
Sizes
1000
2000
3000
4000
5000 *
6000
7500 *
Filter Dimensions x Number of
cells/air flow
(704x327x48) x1 (452x435x48) x2 (552x535x48) x2 (466x685x48) x3 (466x685x48) x3 (566x835x48) x3 (566x835x48) x3
Sizes
10 000 *
15 000 *
Universal dimensions
592 x 592 x 48
3
3
287 x 592 x 48
3
4
Floway “Vertical PHE” filters
Sizes
700
1500
2000
Filter Dimensions x Number of cells/air flow
(330x597x48) x1
(471x697x48) x1
(541x697x48) x1
Dual filtration
When dual-stage filtration is installed, the two stages of cells are installed on the same runner. This assembly is available on
"Classic PHE", "Classic RHE/RHE-Z" and "Vertical PHE" models.
Fan motor assembly
EC motor
This fan motor assembly is a direct coupling type plug fan with
rotation speed adjustment via the portable micro-terminal, or by automatic adaptation
to a given setpoint.
The Floway is equipped with 2 fan motor assemblies: 1 at the intake and 1 at the exhaust. It is also
equipped with 4 fan motor assemblies for the 10,000 and 15,000 sizes of the "Classic RHE/RHE-Z" model
Floway “Classic PHE” and “Classic RHE/RHE-Z”
Sizes
1000
2000
3000
4000 & 5000 6000 & 7500
10000
15000
Turbine type
250 (Alu.)
250 (PP)
280 (Alu.)
280 (PP)
355 (Alu.)
400 (Alu.)
450 (Alu.)
450 (Alu.)
500 (Alu.)
Number of fans per AHU
2
2
2
2
2
2
2
4
4
Nominal capacity (kW)
2x 0,5
2x 0,5
2x 1,04
2x 1,05
2x 1,9
2x 2,5
2x 2,9
4x 2,9
4x 3,8
Rated current (A)
2x 2,2
2x 2,3
2x 1,64
2x 1,6
2x 3
2x 3,8
2x 4,5
4x 4,5
4x 5,9
4 - DESCRIPTION OF THE UNIT & TECHNICAL CHARACTERISTICS
FLOWAY EN-12