Remote On/Off: 2 wires
Machine terminal block
Notes
Inlet/Outlet
Xm 18 _ b-8
Unit ON/OFF monitoring
Dry contact
Digital inputs
Xm 18 _ b-9
►
Setpoint 1/setpoint 2 selection: 2 wires
Machine terminal block
Notes
Inlet/Outlet
Xm 18 _ b-6
Dry-contact setpoint selection
Digital output
Xm 18 _ b-7
►
Air quality sensor: 3 wires
Machine terminal block
Notes
Inlet/Outlet
Xm 19 _ b-5
Shared
Xm 19 _ b-6
Sensor 24V supply
Xm 19 _ b-7
CO2 sensor/transmitter 0-10 V active
rear sensor
Analogue input
►
Fault feedback: 4 wires
Machine terminal block
Notes
Inlet/Outlet
Xm 18 _ b-3
"Danger" fault monitoring
Dry contact (shared b-4)
Digital outputs
Xm 18 _ b-4
Shared
Xm 18 _ b-5
"Maintenance" fault monitoring
Dry contact (shared b-4)
►
Intake duct pressure sensor: 3 wires
Machine terminal block
Notes
Inlet/Outlet
Xm 19 _ b-5
Shared
Xm 19 _ b-6
(IN) sensor 24V supply
Xm 19 _ b-7
(OUT) pressure monitoring signal
0-10 V
Analogue input
INSTALLING THE SIPHON ON CONDENSATE DRAINS
It is important to ensure the siphon is correctly fitted, as per the diagram below. For a depression H in the condensate drain, the
sizing of the siphon must incorporate dimensions of 2H.
Schematic diagram of siphon
Vco
2
GND
Power supply
24 VDC
Controller display or
passive controller
0-10 V output
3-wire tech.
IN
OUT
GND
3
2
1
5 – INSTALLATION AND INSTALLATION CONNECTIONS
FLOWAY EN-30