Additional electrical heater box
Sizes
1
2
2
3
4
4
5
5
Associated
model
Classic PHE/RHE/
RHEZ 1000
Vertical PHE 700
Vertical PHE 1500
Classic PHE/RHE/
RHEZ 2000
Vertical PHE 2000
Classic PHE/RHE/
RHEZ
3000
Classic PHE/RHE/
RHEZ
4000
Classic PHE/RHE/
RHEZ
5000
Classic PHE/RHE/
RHEZ
6000
Classic PHE/RHE/
RHEZ
7500
Voltage
230 V 1-Ph
400 V 3-Ph
Current
19,6
10,4
15,6
18,2
24,2
28,6
32,9
45
Requires a specific dedicated power supply
Connect the unit's electrics to the power network as per the tables above.
Connection to the main circuit breaker located inside the box (Ø 22.2 blanking cover provided).
If there is an electric heater in the additional box, make provision for the electrical connections.
Sizes
1000
2000
3000
5000
7500
Voltage (V)
230 V 1-Ph
400 V 3-Ph
Max. current (A)
5,4
3,6
6,1
8,8
10,3
Minimum power supply cable section
3G1
4G0.75
4G1
4G1.5
4G1.5
Disconnect switch size
OT40 (40 A)
OT63 (63 A)
Max. terminal section (mm
2
)
0,75 to 10
1,5 to 35
Torque Value (N.m)
0,8
2
• Connect the unit's electrics to the power network as per the table above.
• Connection to the machine's general disconnect switch located inside it (Ø 22.2 blanking cover provided).
• For sections between 0.75 and 2.5 mm2, a H 05 VV-F type cable may be used, otherwise the cable must be type H 07 RN-F.
• The power supply cable must be sized in accordance with current standards and regulations.
• The supply cable must be secured using the anchorage provided (located between the disconnect switch and the Ø 22.2
blanking cover). Once the supply cable has been fed through and connect, tighten the clamp fully and cut the end extending
past the clamp.
• Respect the current assigned to the disconnect switch for the air handling unit.
• The leakage current may reach 13 mA. Earthing is essential. Each unit is equipped with 2 earth terminals (PE) indicated by
the logo
, one close to the disconnect switch, and the other on one of the unit's feet. Both terminals must be permanently
connected.
Ø 22.2 blanking cover
Anchorage
Earth terminals
Disconnect
switch
5 – INSTALLATION AND INSTALLATION CONNECTIONS
EN-25 FLOWAY