8 - DIAGNOSTICS
JBus
code
Alarm
code Description
Possible cause
Action taken
Reset type
30
10040
Circuit A Repeated Low Suction Temp Overrides
As above
As above
As above
31
10043
Low Entering Water Temperature In Heating
Low entering fluid
temperature in
Heating mode
No action (alert)
Automatic, if water temperature
returns to normal or heating
mode is stopped
32
10063
Circuit A High pressure switch Failure
High pressure switch
failure
No action (alert)
Manual
33
10097
Water Exchanger Temperature Sensors Swapped Inlet and outlet
temperature reversed
Unit shuts down
Manual
39
57001
Circuit A SIOB Low Voltage Failure
Supply fault
Unit shuts down
Automatic, if supply voltage returns
to normal (up to 6 alarms within 24
hours); otherwise, Manual
40
10215
DHW Antilegionella Setpoint Not Achieved
Low OAT
No action (alert)
Automatic
Master/Slave configuration failure
36
9001
Master Chiller Configuration Error
Configuration failure
Master/slave operation is disabled
and the unit returns to the stand-
alone mode
Automatic, if master/slave
configuration returns to normal or
the unit returns to the standalone
mode
Service and factory
34
130nn
Service Maintenance Alert
01: Service Maintenance Alert
02: Water loop size is low
03: Pump service is required
04: Water filter service
05: Scheduled Service Maintenance date is near
or reached
Servicing action required
/ Contact Manufacturer
Service Agency
Depending on the severity of the
alarm, the unit may continue to
operate or the unit shuts down
Manual (13001-13004) or
Automatic (13005, if the new
maintenance date is set)
35
13006
Fgas check needed, call your maintenance
company
Maintenance date
passed
No action (alert)
Automatic, if the new
maintenance date is set
37
8000
Initial Factory Configuration Required
No factory configuration
Unit cannot be started
Automatic, if configuration is
provided
JBus
code
Alarm
code Description
Possible cause
Action taken
Reset type
38
7001
Illegal Configuration
Incorrect unit
configuration
Unit cannot be started
Automatic, if configuration is
corrected
Drive alarms (variable speed water pump)
Drive alarms for pump drive failure are displayed as 190nn, where “nn” is the alarm code.
The table given below presents the most common alarms associated with the variator malfunction.
Alarm code Description
Action to be taken
01
over current during motor speed increase
Contact Manufacturer Agency
02
over current during motor speed decrease
Contact Manufacturer Agency
03
over current during motor speed hold
Contact Manufacturer Agency
04
over current in drive load
Contact Manufacturer Agency
05
over current in arm
Contact Manufacturer Agency
08
drive inlet phase loss
Contact Manufacturer Agency
09
drive outlet phase loss
Contact Manufacturer Agency
10
over voltage during motor speed increase
Contact Manufacturer Agency
11
over voltage during motor speed decrease
Contact Manufacturer Agency
12
over voltage during motor speed hold
Contact Manufacturer Agency
13
drive overload
Contact Manufacturer Agency
14
motor overload
Contact Manufacturer Agency
16
drive over heat
Contact Manufacturer Agency
17
emergency stop
Contact Manufacturer Agency
18
eeprom #1 alarm
Contact Manufacturer Agency
19
eeprom #2 alarm
Contact Manufacturer Agency
20
eeprom #3 alarm
Contact Manufacturer Agency
21
RAM alarm
Contact Manufacturer Agency
22
ROM alarm
Contact Manufacturer Agency
23
micro-processor alarm
Contact Manufacturer Agency
EN - 27 AQUACIAT