6 - CONNECT TOUCH CONTROL: DETAILED MENU STRUCTURE
Temperature Menu – TEMP
No. Name
Status
Default Unit Displayed text *
Description
1
EWT
-
-
°C
Entering Water Temp.
Evaporator entering water temperature
2
LWT
-
-
°C
Leaving Water Temp.
Evaporator leaving water temperature
3
OAT
-
-
°C
Outside Air Temperature
Outdoor air temperature
4
CHWSTEMP
-
-
°C
Master/Slave Temperature
Hot water system temperature
(used for master/slave assembly control when heating)
5
SCT_A
-
-
°C
Saturated Condensing Tp
Saturated condensing temperature
6
SST_A
-
-
°C
Saturated Suction Temp.
Saturated suction temperature
7
SUCT_A
-
-
°C
Suction Gas Temperature
Suction gas temperature
8
ECO_SST
-
-
°C
Eco. Saturated Suction T
Economizer suction temperature
9
ECO_SUCT
-
-
°C
Economizer Suction Gas T
Economizer suction gas temperature
10
DEFRT_A
-
-
°C
Defrost Temperature A
Defrost temperature 1 – sensor linked to the first fan
11
DEFRT_2
-
-
°C
Defrost Temp Second Coil
Defrost temperature 2 – sensor linked to the second fan
(only for unit size 14, 19, 200, 300)
12
DHW_TT
-
-
°C
DHW Tank Temperature
Domestic hot water tank temperature
*Displayed in French by default.
Pressure Menu – PRESSURE
No. Name
Status
Default Unit Displayed text *
Description
1
DP_A
-
-
kPa
Discharge Pressure
Compressor discharge pressure
2
SP_A
-
-
kPa
Main Suction Pressure
Compressor suction pressure
3
ECO_SP_A
-
-
kPa
Eco. Suction Pressure
Economizer suction pressure
4
5
INTERNAL HYDRONIC MODULE Internal hydronic module
6
W_P_IN
-
-
kPa
Inlet Water Pressure
Inlet water pressure
*Displayed in French by default.
Setpoint Menu – SETPOINT
No. Name
Status
Default Unit Displayed text *
Description
1
hsp1
26.7 to 65.0
65.0
°C
Heating Setpoint 1
Heating setpoint 1 (used during occupied periods)
2
hsp2
26.7 to 65.0
65.0
°C
Heating Setpoint 2
Heating setpoint 2 (used during unoccupied periods)
3
hramp_sp
0.1 to 1.1
0.5
K
Heating Ramp Loading
Ramp loading setpoint (rate at which the water temperature may change
within one minute)
4
lim_sp1
0 to 100
100
%
Switch Limit Setpoint
Setpoint used for capacity limitation
*Displayed in French by default.
Inputs Menu – INPUTS
No. Name
Status
Default Unit Displayed text *
Description
1
ONOFF_SW
open / close
-
-
Remote On/Off Switch
Remote on/off switch
2
SETP_SW
open / close
-
-
Remote Setpoint Switch
Remote setpoint switch
3
LIM_SW1
open / close
-
-
Limit Switch
Demand limit switch
4
LIM_ANAL
-
-
mA
Limit Analog Input
Limit analogue input status
5
FLOW_SW
open / close
-
-
Flow Switch
Flow switch status
6
HP_SW_A
open / close
-
-
HP Switch Circuit A
High pressure switch
7
DHW_REQ
open / close
-
-
DHW Tank Request
Domestic hot water tank request
8
FDBK_A1
open / close
-
-
CPA1 Safety FeedBack
Compressor A1 safety feedback (open contact = compressor is stopped)
9
FDBK_A2
open / close
-
-
CPA2 Safety FeedBack
Compressor A2 safety feedback (open contact = compressor is stopped)
*Displayed in French by default.
EN - 13 AQUACIAT
CALEO