7.1  Start/stop control

The unit state is determined based on a number of factors, 
including its operating type, active overrides, open contacts, 

master/slave configuration, or alarms.

The table given below summarizes the unit control type [ctrl_typ] 
and its running status with regard to the following parameters:

• 

Operating type: 

This operation type is selected using the 

Start/Stop button on the user interface.

 

LOFF

Local off

L-C

Local on

L-SC

Local schedule

Rem

Remote

Net

Network

Mast

Master unit

• 

Start/stop force command

 [CHIL_S_S]: Start/stop force 

command can be used to control the chiller state in the 
Network mode.

Command set to stop:

 The unit is halted.   

Command set to start: 

The unit runs according to schedule 1.

• 

Remote start/stop contact status

 [Onoff_sw]: Start/stop 

contact status can be used to control the chiller state in the 
Remote operating type.

• 

Master control type 

[ms_ctrl]: When the unit is the master 

unit in a two-chiller master/slave arrangement, the master unit 
may be set to be controlled locally, remotely or via network.

• 

Start/stop schedule 

[chil_occ]: Occupied or unoccupied 

status of the unit.

• 

Network emergency stop command 

[EMSTOP]: 

If activated, the unit shuts down regardless of the active 
operating type.

• 

General alarm

: The unit shuts down due to failure.

7.2  Capacity control

The Connect Touch control adjusts the number of active 

compressors  to  keep  the  heat  exchanger  temperature  at  its 

setpoint. The precision with which this is achieved depends on 

the capacity of the water loop, the flow rate, and the load.

7.3  Demand limit

The demand limit functionality is used to limit the unit power 
consumption whenever possible. 

The control allows limitation of the unit capacity:

•  By means of user-controlled volt-free contacts: The unit 

capacity can never exceed the limit setpoint activated by 
these contacts. The limit setpoints can be modified in the 
SETPOINT menu.

• 

By setting DEM_LIM when the unit is in Network mode.

•  By lag limit set by the master unit (master/slave assembly). 

If the unit is not in the Master/Slave assembly, the lag limit 

value is equal to 100%.

Capacity  limitation  is  expressed  in  percentage,  where  a  limit 

value of 100% means that the unit may run with its full capacity 
(no limitation is implemented).

Example: Switch-controlled demand limitation 
(Switch Limit Setpoint in the Setpoint menu)

Switch Limit Setpoint [lim_sp1]

Compressor control

100%

1 × 2 = 2 compressors

Two compressors can be started

75%

0.75 × 2 = 1.5 compressor

One compressor can be started

50%

0.5 × 2 = 1 compressor

One compressor can be started

25%

0.25 × 2 = 0.5 compressor

No compressor can be started

7 - STANDARD CONTROL OPERATIONS AND OPTIONS

Active operating type

Parameters status

Control 

type

Unit 

state

LOFF

L-C

L-SC

Rem

Net

Mast

Start/stop 

force 

command

Remote start/

stop contact

Master 

control type

Start/stop 

schedule

Network 

Emergency 

Shutdown

Alarm 

shutdown

enable

off

yes

off

active

local

off

active

unoccupied

local

off

active

open

remote

off

active

unoccupied

remote

off

active

disable

network

off

active

unoccupied

network

off

active

local

unoccupied

local

off

active

open

remote

remote

off

active

remote

unoccupied

remote

off

active

disable

network

network

off

active

network

unoccupied

network

off

active

disable

no

local

on

active

occupied

disable

no

local

on

active

closed

occupied

disable

no

remote

on

active

enable

occupied

disable

no

network

on

active

local

occupied

disable

no

local

on

active

closed

remote

occupied

disable

no

remote

on

active

enable

network

occupied

disable

no

network

on

IMPORTANT: When the unit is stopping or there is a demand to stop the unit, compressors are stopped consecutively. 

In case of emergency stop, all compressors are stopped at the same time.

 

AQUACIAT

CALEO

 

 EN - 20

 

Содержание AQUACIAT CALEO CONNECT TOUCH

Страница 1: ...Instruction manual AQUACIAT CALEO 14 300 02 2018 10199 CONNECT TOUCH...

Страница 2: ...he user interface provided in this manual include text in English After changing the language of the system all labels will be in the language selected by the user Please read all instructions prior t...

Страница 3: ...ouch buttons 5 4 4 Menu structure 6 5 SETTING UP CONNECT TOUCH CONTROL 7 5 1 General description 7 5 2 Welcome screen 7 5 3 Synoptic screen 7 5 4 Unit start stop 7 5 5 Display settings 8 5 6 Main menu...

Страница 4: ...power source RISK OF BURNS Electrical currents may cause components to get hot Handle the power cable electrical cables and conduits terminal box covers and motor frames with great care 2 1 Control sy...

Страница 5: ...d to monitor the water pressure The pump is protected against cavitation low pump entering pressure 3 5 Temperature sensors Temperature sensors constantly measure the temperature of various components...

Страница 6: ...sed to control the pump and unit operation open pump continues to run closed pump is stopped unit is not allowed to start DHW Tank Request Switch SIOB DI 06 63 64 Used to command the domestic hot wate...

Страница 7: ...ernet connector 3 Modbus RS485 connector 4 Internal bus RS485 5 Power supply connector 24 VAC This RS 485 bus can be used as a second internal bus for the connection of gateway If it is the case then...

Страница 8: ...Configuration User Configuration Pump Configuration Date Time 0 10V Pump Config Heat Cool Config Control Identification Schedule Configuration menu Main menu ModbusRTU Config ModbusTCP IP Config Netwo...

Страница 9: ...ng the table content ACCESS DENIED Equipment controller denies access to one of the tables LIMIT EXCEEDED The value entered exceeds the parameter limit Save changes Modifications have been made The ex...

Страница 10: ...tem allows users to add new languages to the control To learn more about language customization please contact your local service representative 5 5 2 System of measurement The control offers the poss...

Страница 11: ...modifiable parameters such as pump configuration schedule menu etc The Configuration menu is password protected To access the Configuration menu press the Main menu button located in the upper left pa...

Страница 12: ...HEDULE 3 Go to OCCPC01S 4 Select appropriate check boxes to set the unit occupancy on specific days 5 Define the time of occupancy 6 When the time schedule is set the selected period will be presented...

Страница 13: ...the unit cannot be started stopped via the web interface All other operations including monitoring unit parameters or unit configuration can be performed via the web browser interface 5 10 2 Web brow...

Страница 14: ...t selection 5 0 Auto 1 Spt1 2 Spt2 0 Auto schedule control 1 Heating setpoint 1 2 Heating setpoint 2 6 SP_OCC no yes Setpoint Occupied Setpoint occupancy status 7 CHIL_S_S disable enable Net Cmd Start...

Страница 15: ...kPa Eco Suction Pressure Economizer suction pressure 4 5 INTERNAL HYDRONIC MODULE Internal hydronic module 6 W_P_IN kPa Inlet Water Pressure Inlet water pressure Displayed in French by default Setpoi...

Страница 16: ...utput 17 ALARM off on Alarm Relay Status Alarm relay status 18 RUNNING off on Running Relay Status Running relay status 19 DHW_3WV off on DHW 3 Way Water Valve DHW 3 way water valve Displayed in Frenc...

Страница 17: ...splayed in French by default Domestic Hot Water Menu DHW_STAT No Name Status Default Unit Displayed text Description 1 dhw_mode 0 to 2 Mode Mode 2 0 SHC 1 DHW 2 AntiLeg 0 Space Heating Control SHC 1 D...

Страница 18: ...de additional features some tables may contain parameters that cannot be configured for a given unit General Config Menu GENCONF No Name Status Default Unit Displayed text Description 1 ramp_sel no ye...

Страница 19: ...set Value OAT max reset value 3 dt_hr_no 0 to 14 0 K Delta T No Reset Value Delta T no reset value 4 dt_hr_fu 0 to 14 0 K Delta T Full Reset Value Delta T max reset value 5 I_hr_no 0 to 20 0 mA Curren...

Страница 20: ...tware version 4 xx chars MAC address Serial Number Serial number MAC address Displayed in French by default 0 10V Pump Config Menu FLOWCONF No Name Status Default Unit Displayed text Description 1 log...

Страница 21: ...Parity High 4 Force Parity High 17 stop_bit 0 to 1 0 Stop bit Stop bit 18 0 One Stop Bit 0 One Stop Bit 19 1 two Stop Bits 1 Two Stop Bits 20 real_typ 0 to 1 1 Real type management Real type managemen...

Страница 22: ...y can never exceed the limit setpoint activated by these contacts The limit setpoints can be modified in the SETPOINT menu By setting DEM_LIM when the unit is in Network mode By lag limit set by the m...

Страница 23: ...d through the LEN drive The status of the internal pump is displayed in the Pump Status menu under Drive pump status External Pump Output PUMP_EXT Pump Status menu and External Pump Output PUMP_EXT Ou...

Страница 24: ...trol point is modified so that the machine capacity required is adjusted to be as close as possible to the demand The reset source can be provided by one of the following Outdoor air temperature that...

Страница 25: ...ng mode if at least one of the following conditions applies The volt free tank request contact is open The maximum operating time for the DHW mode has elapsed Time schedule 3 is in an unoccupied perio...

Страница 26: ...eating stage will not be used even if the heating demand cannot be satisfied This electric heating backup option can be enabled by setting 1 Elec Stage For Backup ehs_back to yes in the Heat Cool Conf...

Страница 27: ...ory Basic Reset Alarms User 8 2 Displaying current alarms The Current alarms menu may display up to 10 current alarms To access the list of currently active alarms 1 Press the Alarm button in the uppe...

Страница 28: ...e 15 4901 Loss of communication with SIOB Board Number A Bus installation fault communication error Unit shuts down Automatic if communication is re established 16 4601 Loss of communication with AUX1...

Страница 29: ...company Maintenance date passed No action alert Automatic if the new maintenance date is set 37 8000 Initial Factory Configuration Required No factory configuration Unit cannot be started Automatic if...

Страница 30: ...ed increase Contact Manufacturer Agency 38 over current during product speed decrease Contact Manufacturer Agency 39 over current during product speed hold Contact Manufacturer Agency 41 drive type er...

Страница 31: ...erious damage can occur to your equipment TheManufacturerprovidesawiderangeofservicecontractswhich embrace the assistance of highly qualified HVAC engineering professionals ready to help if needed The...

Страница 32: ...ompagnie Industrielle d Applications Thermiques S A au capital de 26 728 480 R C S Bourg en Bresse B 545 620 114 Non contractual document With the thought of material improvement always in mind CIAT r...

Отзывы: