6  -  CONNECT TOUCH CONTROL: DETAILED MENU STRUCTURE

 

Heat/Cool Config Menu – HCCONFIG

No. Name

Status

Default Unit Displayed text *

Description

1

hr_sel

0 to 3

1

-

Heating Reset Select

Heating reset selection

2

0=None,    1=OAT

0 = None 

1 = OAT 

3

 2=Delta T, 3=4-20mA

2 = Delta T (LWT-EWT) 

3 = 4-20 mA control (external temperature sensor)

4

min_th

-25 to 0

-20

°C

Minimum OAT Threshold

Minimum OAT threshold (used for unit protection control)

5

max_th

5 to 100

100

°C

Maximum OAT Threshold

Maximum OAT threshold (used to define the Summer mode)

6

boil_th

-30 to 15

-10

°C

Boiler OAT Threshold

Boiler OAT threshold

7

ehs_th

-5 to 21

5

°C

Elec Stage OAT Threshold

Electric heating stage, OAT threshold

8

ehs_back

no / yes

no

-

1 Elec Stage For Backup

One electric heating stage used for back-up

9

ehs_pull

0 to 60

0

min

Electrical Pulldown Time

Electrical pull-down time 

10

ehs_defr

no / yes

no

-

Quick EHS For Defrost

Quick EHS for defrost enabled

*Displayed in French by default.

 

Reset Configuration Menu – RESETCFG

No. Name

Status

Default Unit Displayed text *

Description

1

oathr_no 

-20 to 52 

-10

°C

OAT No Reset Value

OAT, no reset value

2

oathr_fu

-20 to 52

-20

°C

OAT Full Reset Value

OAT, max. reset value

3

dt_hr_no

0 to 14

0

K

Delta T No Reset Value

Delta T, no reset value

4

dt_hr_fu

0 to 14

0

K

Delta T Full Reset Value

Delta T, max. reset value

5

I_hr_no

0 to 20

0

mA

Current No Reset Value

Current, no reset value

6

I_hr_fu

0 to 20

0

mA

Current Full Reset Value

Current, max. reset value

7

hr_deg

-30 to 30

10

K

Heating Reset Deg. Value

Heating reset value

*Displayed in French by default.

 

User Configuration Menu – USERCONF

No. Name

Status

Default Unit Displayed text *

Description

1

use_pass

0 to 9999

11

-

User Password

User password: The user password can be modified by changing the value 

in this line

*Displayed in French by default.

 

Schedule Menu – SCHEDULE

No. Name

Status

Default Unit Displayed text *

Description

1

OCCPC01S

-

-

-

OCCPC01S - Schedule Menu

Unit on/off time schedule

2

OCCPC02S

-

-

-

OCCPC02S - Schedule Menu

Unit setpoint selection time schedule

3

OCCPC03S

-

-

-

OCCPC03S - Schedule Menu

Domestic hot water production schedule

4

OCCPC04S

-

-

-

OCCPC04S - Schedule Menu

Anti-legionella treatment schedule

*Displayed in French by default.

 

Holiday Menu – HOLIDAY

No. Name

Status

Default Unit Displayed text *

Description

1

HOL_MON

0-12

0

-

Holiday Start Month

Holiday start month

2

HOL_DAY

0-31

0

-

Start Day

Holiday start day

3

HOL_LEN

0-99

0

-

Duration (days)

Holiday duration (days)

*Displayed in French by default.

 

 

EN - 17 AQUACIAT

CALEO

Содержание AQUACIAT CALEO CONNECT TOUCH

Страница 1: ...Instruction manual AQUACIAT CALEO 14 300 02 2018 10199 CONNECT TOUCH...

Страница 2: ...he user interface provided in this manual include text in English After changing the language of the system all labels will be in the language selected by the user Please read all instructions prior t...

Страница 3: ...ouch buttons 5 4 4 Menu structure 6 5 SETTING UP CONNECT TOUCH CONTROL 7 5 1 General description 7 5 2 Welcome screen 7 5 3 Synoptic screen 7 5 4 Unit start stop 7 5 5 Display settings 8 5 6 Main menu...

Страница 4: ...power source RISK OF BURNS Electrical currents may cause components to get hot Handle the power cable electrical cables and conduits terminal box covers and motor frames with great care 2 1 Control sy...

Страница 5: ...d to monitor the water pressure The pump is protected against cavitation low pump entering pressure 3 5 Temperature sensors Temperature sensors constantly measure the temperature of various components...

Страница 6: ...sed to control the pump and unit operation open pump continues to run closed pump is stopped unit is not allowed to start DHW Tank Request Switch SIOB DI 06 63 64 Used to command the domestic hot wate...

Страница 7: ...ernet connector 3 Modbus RS485 connector 4 Internal bus RS485 5 Power supply connector 24 VAC This RS 485 bus can be used as a second internal bus for the connection of gateway If it is the case then...

Страница 8: ...Configuration User Configuration Pump Configuration Date Time 0 10V Pump Config Heat Cool Config Control Identification Schedule Configuration menu Main menu ModbusRTU Config ModbusTCP IP Config Netwo...

Страница 9: ...ng the table content ACCESS DENIED Equipment controller denies access to one of the tables LIMIT EXCEEDED The value entered exceeds the parameter limit Save changes Modifications have been made The ex...

Страница 10: ...tem allows users to add new languages to the control To learn more about language customization please contact your local service representative 5 5 2 System of measurement The control offers the poss...

Страница 11: ...modifiable parameters such as pump configuration schedule menu etc The Configuration menu is password protected To access the Configuration menu press the Main menu button located in the upper left pa...

Страница 12: ...HEDULE 3 Go to OCCPC01S 4 Select appropriate check boxes to set the unit occupancy on specific days 5 Define the time of occupancy 6 When the time schedule is set the selected period will be presented...

Страница 13: ...the unit cannot be started stopped via the web interface All other operations including monitoring unit parameters or unit configuration can be performed via the web browser interface 5 10 2 Web brow...

Страница 14: ...t selection 5 0 Auto 1 Spt1 2 Spt2 0 Auto schedule control 1 Heating setpoint 1 2 Heating setpoint 2 6 SP_OCC no yes Setpoint Occupied Setpoint occupancy status 7 CHIL_S_S disable enable Net Cmd Start...

Страница 15: ...kPa Eco Suction Pressure Economizer suction pressure 4 5 INTERNAL HYDRONIC MODULE Internal hydronic module 6 W_P_IN kPa Inlet Water Pressure Inlet water pressure Displayed in French by default Setpoi...

Страница 16: ...utput 17 ALARM off on Alarm Relay Status Alarm relay status 18 RUNNING off on Running Relay Status Running relay status 19 DHW_3WV off on DHW 3 Way Water Valve DHW 3 way water valve Displayed in Frenc...

Страница 17: ...splayed in French by default Domestic Hot Water Menu DHW_STAT No Name Status Default Unit Displayed text Description 1 dhw_mode 0 to 2 Mode Mode 2 0 SHC 1 DHW 2 AntiLeg 0 Space Heating Control SHC 1 D...

Страница 18: ...de additional features some tables may contain parameters that cannot be configured for a given unit General Config Menu GENCONF No Name Status Default Unit Displayed text Description 1 ramp_sel no ye...

Страница 19: ...set Value OAT max reset value 3 dt_hr_no 0 to 14 0 K Delta T No Reset Value Delta T no reset value 4 dt_hr_fu 0 to 14 0 K Delta T Full Reset Value Delta T max reset value 5 I_hr_no 0 to 20 0 mA Curren...

Страница 20: ...tware version 4 xx chars MAC address Serial Number Serial number MAC address Displayed in French by default 0 10V Pump Config Menu FLOWCONF No Name Status Default Unit Displayed text Description 1 log...

Страница 21: ...Parity High 4 Force Parity High 17 stop_bit 0 to 1 0 Stop bit Stop bit 18 0 One Stop Bit 0 One Stop Bit 19 1 two Stop Bits 1 Two Stop Bits 20 real_typ 0 to 1 1 Real type management Real type managemen...

Страница 22: ...y can never exceed the limit setpoint activated by these contacts The limit setpoints can be modified in the SETPOINT menu By setting DEM_LIM when the unit is in Network mode By lag limit set by the m...

Страница 23: ...d through the LEN drive The status of the internal pump is displayed in the Pump Status menu under Drive pump status External Pump Output PUMP_EXT Pump Status menu and External Pump Output PUMP_EXT Ou...

Страница 24: ...trol point is modified so that the machine capacity required is adjusted to be as close as possible to the demand The reset source can be provided by one of the following Outdoor air temperature that...

Страница 25: ...ng mode if at least one of the following conditions applies The volt free tank request contact is open The maximum operating time for the DHW mode has elapsed Time schedule 3 is in an unoccupied perio...

Страница 26: ...eating stage will not be used even if the heating demand cannot be satisfied This electric heating backup option can be enabled by setting 1 Elec Stage For Backup ehs_back to yes in the Heat Cool Conf...

Страница 27: ...ory Basic Reset Alarms User 8 2 Displaying current alarms The Current alarms menu may display up to 10 current alarms To access the list of currently active alarms 1 Press the Alarm button in the uppe...

Страница 28: ...e 15 4901 Loss of communication with SIOB Board Number A Bus installation fault communication error Unit shuts down Automatic if communication is re established 16 4601 Loss of communication with AUX1...

Страница 29: ...company Maintenance date passed No action alert Automatic if the new maintenance date is set 37 8000 Initial Factory Configuration Required No factory configuration Unit cannot be started Automatic if...

Страница 30: ...ed increase Contact Manufacturer Agency 38 over current during product speed decrease Contact Manufacturer Agency 39 over current during product speed hold Contact Manufacturer Agency 41 drive type er...

Страница 31: ...erious damage can occur to your equipment TheManufacturerprovidesawiderangeofservicecontractswhich embrace the assistance of highly qualified HVAC engineering professionals ready to help if needed The...

Страница 32: ...ompagnie Industrielle d Applications Thermiques S A au capital de 26 728 480 R C S Bourg en Bresse B 545 620 114 Non contractual document With the thought of material improvement always in mind CIAT r...

Отзывы: