7  -  STANDARD CONTROL OPERATIONS AND OPTIONS

7.7  Additional space heating control

The control provides additional heating control by means of the 
optional boiler or standard electric heating management.

7.7.1  Boiler control (optional)

The boiler can be activated as a heating replacement of a 
heat pump when the operating conditions are not suitable for 
mechanical heating. The unit and the boiler cannot operate 
together at the same time.

The boiler is running under the following conditions:

•  The unit is in heating mode, but a fault prevents the use of 

the heat pump capacity.

•  The unit is in heating mode, but works at a very low outdoor 

temperature, making the heat pump capacity insufficient. It is 

possible to adjust the boiler start-up based on the outside 
temperature. By default, the boiler is started when the outside 

air temperature is -10°C. This threshold can be modified by 
logged-in users in the Heat/Cool Config menu (HCCONFIG).

To set boiler OAT threshold

1. Navigate to the Configuration menu.
2. Select 

Heat/Cool Config

 (HCCONFIG).

3. Set 

Boiler OAT Threshold 

[boil_th].

Boiler OAT Threshold [boil_th]
-30 to 15°C

-10°C

7.7.2  Electric heating control 

Up to 4 stages of electric heating can be activated as supplemental 
or replacement heating when the operating conditions are not 
suitable for the mechanical heating. 

Electric heating is used to supplement mechanical heating 

under the following conditions:

•  The unit uses 100% of its available heating capacity:

• 

The outside temperature is below a configurable 
threshold: “Elec Stage OAT Threshold” [ehs_th].

•  The electrical pulldown time elapsed:  

“Electrical Pulldown Time” [ehs_pull].

•  The unit cannot fully satisfy current heating demand due to 

the protection mode, e.g. low entering water temperature.

To set Electric heating stage OAT threshold

1. Navigate to the Configuration menu.
2. Select 

Heat/Cool Configuration 

(HCCONFIG).

3. Set 

Elec Stage OAT Threshold

 [ehs_th].

Elec Stage OAT Threshold [ehs_th]
-5 to 21°C

5°C

To set Electric Pulldown Time

1. Navigate to the Configuration menu.
2. Select 

Heat/Cool Configuration 

(HCCONFIG).

3. Set 

Electrical Pulldown Time 

[ehs_pull].

Electrical Pulldown Time [ehs_pull]
0 to 60 min

Depending on user configuration, the last electric heating stage 

can be used for back-up when the unit is shut down because of 
the unit failure or operating envelope protection. Otherwise, this 
electric heating stage will not be used even if the heating demand 

cannot be satisfied. This electric heating backup option can be 
enabled by setting “1 Elec Stage For Backup” [ehs_back] to “yes” 
in the Heat/Cool Configuration menu (HCCONFIG).

7.8  Defrost control

When the outside air temperature is low and the ambient 
humidity is high, the probability of frost forming on the surface 
of the outdoor coil increases. The frost covering the outdoor 

coil may decrease the air flow across the coil and lead to lower 

performance of the unit. To remove the frost from the coil, 
the control initiates the defrost cycle when necessary.

7.8.1  Standard defrost

During the defrost cycle, the circuit is forced into the cooling 

mode. The heat (energy) is extracted from the water circuit by 

using compressors and reversing the 4-way valve. To prevent the 
water loop from cooling down, optional electric heating may be 
started. The defrost cycle lasts until the end of defrost temperature 
is achieved.

7.8.2  Free defrost

Free defrost is used in order to eliminate a relatively small 
amount of frost that has formed on the surface of the coil. 

Contrary to the standard defrost session; in the case of the free 

defrost session the heat (energy) is absorbed from the air. When 
running the free defrost, fans are activated and compressors are 

turned off. The free defrost is most efficient when the outside air 

temperature is above 1°C. 

IMPORTANT: In the case of a large amount of frost 

covering the coil, the standard defrost cycle will be started.

7.9  Master/Slave control 

The control system allows for master/slave control of two units 
linked by the network. The master unit can be controlled locally, 
remotely or by network commands, while the slave unit remains 
in Network mode.

All control commands to the master/slave assembly (start/stop, 
setpoint selection, heating control, load shedding, etc.) are handled 

by the unit which is configured as the master. The commands are 

transmitted automatically to the slave unit.

If the master chiller is turned off, while the master/slave function 
is active, then the slave chiller will be stopped. Under certain 

circumstances, the slave unit may be started first to ensure that 

the run times of the two units are equalised.

In the event of a communication failure between the two units, 
each unit will return to an autonomous operating mode until the 
fault is cleared. If the master unit is stopped due to an alarm, 
the slave unit is authorised to start.

IMPORTANT: Master/slave assembly can be configured 

only by service technicians.

 

AQUACIAT

CALEO

 

 EN - 24

 

Содержание AQUACIAT CALEO CONNECT TOUCH

Страница 1: ...Instruction manual AQUACIAT CALEO 14 300 02 2018 10199 CONNECT TOUCH...

Страница 2: ...he user interface provided in this manual include text in English After changing the language of the system all labels will be in the language selected by the user Please read all instructions prior t...

Страница 3: ...ouch buttons 5 4 4 Menu structure 6 5 SETTING UP CONNECT TOUCH CONTROL 7 5 1 General description 7 5 2 Welcome screen 7 5 3 Synoptic screen 7 5 4 Unit start stop 7 5 5 Display settings 8 5 6 Main menu...

Страница 4: ...power source RISK OF BURNS Electrical currents may cause components to get hot Handle the power cable electrical cables and conduits terminal box covers and motor frames with great care 2 1 Control sy...

Страница 5: ...d to monitor the water pressure The pump is protected against cavitation low pump entering pressure 3 5 Temperature sensors Temperature sensors constantly measure the temperature of various components...

Страница 6: ...sed to control the pump and unit operation open pump continues to run closed pump is stopped unit is not allowed to start DHW Tank Request Switch SIOB DI 06 63 64 Used to command the domestic hot wate...

Страница 7: ...ernet connector 3 Modbus RS485 connector 4 Internal bus RS485 5 Power supply connector 24 VAC This RS 485 bus can be used as a second internal bus for the connection of gateway If it is the case then...

Страница 8: ...Configuration User Configuration Pump Configuration Date Time 0 10V Pump Config Heat Cool Config Control Identification Schedule Configuration menu Main menu ModbusRTU Config ModbusTCP IP Config Netwo...

Страница 9: ...ng the table content ACCESS DENIED Equipment controller denies access to one of the tables LIMIT EXCEEDED The value entered exceeds the parameter limit Save changes Modifications have been made The ex...

Страница 10: ...tem allows users to add new languages to the control To learn more about language customization please contact your local service representative 5 5 2 System of measurement The control offers the poss...

Страница 11: ...modifiable parameters such as pump configuration schedule menu etc The Configuration menu is password protected To access the Configuration menu press the Main menu button located in the upper left pa...

Страница 12: ...HEDULE 3 Go to OCCPC01S 4 Select appropriate check boxes to set the unit occupancy on specific days 5 Define the time of occupancy 6 When the time schedule is set the selected period will be presented...

Страница 13: ...the unit cannot be started stopped via the web interface All other operations including monitoring unit parameters or unit configuration can be performed via the web browser interface 5 10 2 Web brow...

Страница 14: ...t selection 5 0 Auto 1 Spt1 2 Spt2 0 Auto schedule control 1 Heating setpoint 1 2 Heating setpoint 2 6 SP_OCC no yes Setpoint Occupied Setpoint occupancy status 7 CHIL_S_S disable enable Net Cmd Start...

Страница 15: ...kPa Eco Suction Pressure Economizer suction pressure 4 5 INTERNAL HYDRONIC MODULE Internal hydronic module 6 W_P_IN kPa Inlet Water Pressure Inlet water pressure Displayed in French by default Setpoi...

Страница 16: ...utput 17 ALARM off on Alarm Relay Status Alarm relay status 18 RUNNING off on Running Relay Status Running relay status 19 DHW_3WV off on DHW 3 Way Water Valve DHW 3 way water valve Displayed in Frenc...

Страница 17: ...splayed in French by default Domestic Hot Water Menu DHW_STAT No Name Status Default Unit Displayed text Description 1 dhw_mode 0 to 2 Mode Mode 2 0 SHC 1 DHW 2 AntiLeg 0 Space Heating Control SHC 1 D...

Страница 18: ...de additional features some tables may contain parameters that cannot be configured for a given unit General Config Menu GENCONF No Name Status Default Unit Displayed text Description 1 ramp_sel no ye...

Страница 19: ...set Value OAT max reset value 3 dt_hr_no 0 to 14 0 K Delta T No Reset Value Delta T no reset value 4 dt_hr_fu 0 to 14 0 K Delta T Full Reset Value Delta T max reset value 5 I_hr_no 0 to 20 0 mA Curren...

Страница 20: ...tware version 4 xx chars MAC address Serial Number Serial number MAC address Displayed in French by default 0 10V Pump Config Menu FLOWCONF No Name Status Default Unit Displayed text Description 1 log...

Страница 21: ...Parity High 4 Force Parity High 17 stop_bit 0 to 1 0 Stop bit Stop bit 18 0 One Stop Bit 0 One Stop Bit 19 1 two Stop Bits 1 Two Stop Bits 20 real_typ 0 to 1 1 Real type management Real type managemen...

Страница 22: ...y can never exceed the limit setpoint activated by these contacts The limit setpoints can be modified in the SETPOINT menu By setting DEM_LIM when the unit is in Network mode By lag limit set by the m...

Страница 23: ...d through the LEN drive The status of the internal pump is displayed in the Pump Status menu under Drive pump status External Pump Output PUMP_EXT Pump Status menu and External Pump Output PUMP_EXT Ou...

Страница 24: ...trol point is modified so that the machine capacity required is adjusted to be as close as possible to the demand The reset source can be provided by one of the following Outdoor air temperature that...

Страница 25: ...ng mode if at least one of the following conditions applies The volt free tank request contact is open The maximum operating time for the DHW mode has elapsed Time schedule 3 is in an unoccupied perio...

Страница 26: ...eating stage will not be used even if the heating demand cannot be satisfied This electric heating backup option can be enabled by setting 1 Elec Stage For Backup ehs_back to yes in the Heat Cool Conf...

Страница 27: ...ory Basic Reset Alarms User 8 2 Displaying current alarms The Current alarms menu may display up to 10 current alarms To access the list of currently active alarms 1 Press the Alarm button in the uppe...

Страница 28: ...e 15 4901 Loss of communication with SIOB Board Number A Bus installation fault communication error Unit shuts down Automatic if communication is re established 16 4601 Loss of communication with AUX1...

Страница 29: ...company Maintenance date passed No action alert Automatic if the new maintenance date is set 37 8000 Initial Factory Configuration Required No factory configuration Unit cannot be started Automatic if...

Страница 30: ...ed increase Contact Manufacturer Agency 38 over current during product speed decrease Contact Manufacturer Agency 39 over current during product speed hold Contact Manufacturer Agency 41 drive type er...

Страница 31: ...erious damage can occur to your equipment TheManufacturerprovidesawiderangeofservicecontractswhich embrace the assistance of highly qualified HVAC engineering professionals ready to help if needed The...

Страница 32: ...ompagnie Industrielle d Applications Thermiques S A au capital de 26 728 480 R C S Bourg en Bresse B 545 620 114 Non contractual document With the thought of material improvement always in mind CIAT r...

Отзывы: