REMOTE EQUIPMENT POWER OFF
Figure - 24 Remote Equipment Power Off (REPO)
To wire the external EPO circuit, connect a normally closed (N/C) emergency switch, which opens when activated and is
held open mechanically when operated. Make sure switch is de-activated (closed) before connecting to the outer terminals
of the EPO terminal block (REPO Hi and REPO Low). Remove the jumper wire between the inner terminals (Disable). It is
recommended to use twisted wires for this low voltage connection.