background image

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

28-2TITAN0019 

 

 

 

 

USER MANUAL 

ON LINE UPS 

1-10KVA 

 

 

 

 

 

 

 

 

 

 

 

 

Uninterruptible Power Supply 

Содержание 1-10KVA

Страница 1: ...28 2TITAN0019 USER MANUAL ON LINE UPS 1 10KVA Uninterruptible Power Supply ...

Страница 2: ...1 Electrical Specifications 13 8 2 Operating Environment 13 8 3 Typical Stored Energy Time Typical values at 25 C in minutes 13 8 4 Dimensions and Weights 14 9 Introduction 6K S 10K S 15 9 1 Product Specification and Performance 15 10 Installation 16 19 10 1 Unpacking and Inspection 16 10 2 Input and Output Power Cords and Protective Earth Ground Installation 16 17 10 3 Operating Procedure for Con...

Страница 3: ...Mode for all Models 28 29 16 Communication Port 30 17 Software for All Models 31 18 Appendix 32 36 Appendix1 Display Panel for 6K S 10K S 32 Appendix2 The Corresponding Form of the LED Display for 6K S 10K S 33 Appendix3 Back Panel 35 36 ...

Страница 4: ...ower cord into mains socket before using of UPS Connect the UPS only to an earthed shockproof socket outlet The building wiring socket outlet shockproof socket outlet must be easily accessible to close to the UPS This is operator installable For 6KVA 10KVA UPS has provided earthed terminal in the final installed system configuration equipotential earth bonding to the external UPS battery cabinets ...

Страница 5: ...ut any kind of service and or maintenance disconnect the batteries Verify that no current is present and no hazardous voltage exists in the capacitor or BUS capacitor terminals Batteries must be replaced only by qualified personnel Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the ground Veri...

Страница 6: ... Voltage Fluctuation and Flicker IEC EN 61000 3 3 EMS ESD IEC EN 61000 4 2 Level 4 RS IEC EN 61000 4 3 Level 3 EFT IEC EN 61000 4 4 Level 4 SURGE IEC EN 61000 4 5 Level 4 Low Frequency Signals IEC EN 61000 2 2 For 6KVA 10KVA Safety IEC EN 62040 1 1 EMI Conducted Emission IEC EN 50091 2 Current 25A Radiated Emission IEC EN 50091 2 Current 25A EMS ESD IEC EN 61000 4 2 Level 4 RS IEC EN 61000 4 3 Lev...

Страница 7: ...4 2 Description of commonly used symbols Some or all of the following symbols may be used in this manual It is advisable to familiarize yourself with them and understand their meaning ...

Страница 8: ... the batteries and powers the inverter On the basis of this DC voltage the inverter generates a sinusoidal AC voltage which permanently supplies the loads Computers and periphery are thus powered entirely by the mains voltage In the event of power failure the maintenance free batteries power the inverter This manual covers the UPS listed as follows Please confirm whether it is the model you intend...

Страница 9: ...tolerance BATTERY LED The orange coloured BATTERY LED lights up when the mains power has failed and the inverter is being powered by the batteries BYPASS LED The orange coloured BYPASS LED lights up when the UPS system is supplying voltage provided by the mains power via the bypass INVERTER LED The green coloured INVERTER LED lights up if the UPS system is supplying voltage provided by the mains p...

Страница 10: ...tput of 1K S and 2KS Non CE are socket types only Simply plug the load power cord to the output sockets to complete connection Model No Output Socket pcs Terminal Block 1K 1KS 4 Nil 2K 6 Nil 2KS 4 CE 6 Non CE Available CE Nil Non CE 3K 3KS 4 CE 3 Non CE Available Besides output sockets 2KS CE and 3K 3KS has the terminal block available for output as well The wiring configuration is shown as the fo...

Страница 11: ...this time the Utility Power LED Inverter LED and Load and Battery Capacity LEDs will light up 4 2 Without utility power connecting Even though utility power is connected to the UPS the UPS still can be turned on by just simply pressing I button continuously for more than 1 second Then the UPS will get into self test status first After having finishing the self test the UPS will get into the invert...

Страница 12: ...required will cause abnormality 2 One end of the external battery cord is a plug for connecting the UPS and the other end has a plug for connecting the user battery cabinet 3 Do not connect the UPS to any load yet Then connect the power cord of the UPS to supply utility power to the UPS to make the UPS operate in utility power mode 4 Connect the plug of the external battery cord to the external ba...

Страница 13: ...d of the UPS to supply utility power to the UPS to make the UPS operation in utility power mode 8 Plug the external battery cord to the external battery socket on the rear panel of the UPS to complete the connection procedure and the UPS will start to charge the battery pack The Caution The output sockets of the UPS system may still be electrically live even if the power supply system has been dis...

Страница 14: ...On Switch I INVERTER LED lights up and audible alarm sounding every 1 beep in every 4 seconds Mains power supply has failed Switching to battery mode automatically When audible alarm sounding every second battery is almost empty FAULT LED lights warning tone once a second Overload Remove loads of UPS output FAULT LED lights up permanent warning tone UPS fault Notify dealer Emergency supply period ...

Страница 15: ...mbient temperature has been exceeded the batteries must be replaced In this case please contact your dealer 7 2 Storage If the batteries are stored in temperate climatic zones they should be charged every three months for 1 2 hours You should shorten the charging intervals to two months at locations subject to high temperatures ...

Страница 16: ...kW Voltage 220 230 240 1 士 2 VAC Frequency 50Hz 0 2Hz Battery mode Wave form sinusoidal BATTERIES Model No 1K 2K 3K Number and type 3 12V 7 2Ah 8 12V 7 2Ah 8 12V 7 2Ah 8 2 Operating Environment Ambient Temperature 0 o C to 40 o C Operating humidity 95 Altitude 1000m Storage temperature 0 o C 40 o C 8 3 Typical stored energy time Typical values at 25 C in minutes Model No 100 Load 50 Load 1K 5 14 2...

Страница 17: ...8 Technical Data 8 4 Dimensions and weights Model No Dimensions W x D x H mm Net Weight kg 1K 145X400X220 14 1KS 145X400X220 7 2K 192X460X340 34 5 2KS 192X460X340 15 3K 192X460X340 35 5 3KS 192X460X340 16 ...

Страница 18: ...wer Factor 6K S 10K S Single phase 46Hz 54Hz 0 98 Full load Output Voltage Regulation Power Factor Frequency tolerance Distortion Overload capacity Current crest ratio 1 0 7 lag Synchronized 46 54Hz in Line mode AC mode 0 1 of normal frequency in Battery mode THD 2 Full load Linear Load 105 130 load transfers to bypass mode after 10 minutes 130 load transfers to bypass mode after 1 second and shut...

Страница 19: ...ops may occur if the UPS is unpacked in a very low temperature environment In this case it is necessary to wait until the UPS is fully dried inside out before proceeding installation and use Otherwise there are hazards of electric shock 2 Installation Installation and wiring must be performed in accordance with the local electric code and the following instructions by professional personnel For sa...

Страница 20: ...at the output power distribution panel of the UPS if necessary 8 To connect the load with the UPS please turn off all the loads first then perform the connection and finally turn on the loads one by one 9 No matter the UPS is connected to the utility power or not the output of the UPS may have electricity The parts inside the unit may still have hazardous voltage after turning off the UPS To make ...

Страница 21: ...specified in the general specification 2 Set the battery pack breaker in OFF position and connect the 20 pieces of batteries in series 3 You must connect the external battery cable to the battery first if you connect the cable to the UPS first you may encounter the hazardous of electric shock The positive pole of the battery is connected to the 10KS in parallel with blue and brown wires the negati...

Страница 22: ...ich should have 25 cores corresponding stitches and shield as the UPS parallel cable The length of the parallel cable is appropriate to be less than 3 m 2 Strictly follow the stand alone wiring requirement to perform the input wiring of each UPS 3 Connect the output wires of each UPS to an output breaker panel 4 Disconnect the Jumper on JP1 and JP2 of the terminal block first and connect each outp...

Страница 23: ...UPS with utility power supplied in Line mode AC mode 1 After you make sure that the power supply connection is correct set the bypass breaker and the input breaker in the ON position first At this time the fan rotates and the UPS supplies power to the load via the bypass The UPS operates in Bypass mode 2 To power on the UPS by simply pressing the ON button continuously for more than 1 second 3 Whe...

Страница 24: ...m self diagnosis finally not any display is shown on the display panel and no voltage output is available from the UPS output 4 Turn off the UPS with no utility power supplied in Battery mode 1 Press the OFF button continuously for more than 1 second to power off the UPS 2 When being powered off the UPS will perform self diagnosis the Load Battery level LEDs will be turned on and then off one afte...

Страница 25: ...and output live wire of parallel system If the voltage difference 1V please close output live wire s witch of new UPS 7 Take apart the board of parallel ports when UPS has turned to bypass mode insert the other end of combine line into parallel card s slot and screw down its pin and then lock up the board of parallel ports over again 8 Close line input switch of all UPS include new UPS in the para...

Страница 26: ... parallel cover and combine line connected with the UPS which need to remove until all UPS panels become black then lock up the cover of parallel ports again 6 Take apart UPS parallel cover and combine line when the UPS have to remove then lock up the cover of parallel ports again 7 Shut input line switch of leaving UPS system turn maintain switch from BPS to UPS until all UPS turn to BPS mode and...

Страница 27: ...he long backup time model is dependent on the external battery pack capacity and the load level as well as other factors The backup time of standard model may vary from different models and load level Please refer to the following Load level backup time of 6kVA Load level backup time of 10kVA ...

Страница 28: ...regions of hot climates the battery should be charged and discharged every 2 months The standard charging time should be at least 12 hours l Under normal conditions the battery life lasts 3 to 5 years In case if the battery is found not in good condition earlier replacement should be made Battery replacement should be performed by qualified personnel l Replace batteries with the same number and sa...

Страница 29: ...rode otherwise it may result in electric shock or fire 6 Make sure that there is no voltage before touching the batteries The battery circuit is not isolated from the input potential circuit There may be hazardous voltage between the battery terminals and the ground 7 Even though the input breaker is disconnected the components inside the UPS are still connected with the batteries and there are po...

Страница 30: ...ment is faulty Check the loads and remove all no critical equipment Recalculate the load power and reduce the number of loads connected to the UPS Check that the loads are not failed The 1 Fault LED is turned on and the battery LED is flashed the buzzer beeps every second The charger of the UPS is defective Please contact the distributor or service center Battery LED flashes Battery low or battery...

Страница 31: ...eration is stable before supplying power of the generator to the UPS be sure that the UPS is in idle mode Then turn on the UPS according to the start up procedure After the UPS is turned on then the loads can be connected to the UPS one by one l The power capacity of the AC generator should be at least twice of the UPS capacity 2 Battery mode The display panel in battery mode is shown in the follo...

Страница 32: ...y power LED and the bypass LED are lit The displayed number of the load LEDs will be turned on in accordance with the load capacity connected The UPS will beep once every 2 minutes in bypass mode The utility power LED flashes it shows that the voltage or frequency of the utility power has exceeded the normal range of the UPS 1 Other indications on the display panel are the same in utility mode 2 T...

Страница 33: ...his series UPS has AS400 card an optional accessory for AS400 communication protocol Please contact your local distributor for details The following is the pin assignment and description of DB 9 connector in AS400 card Pin Description I O 1 UPS Fail Output 2 Summary Alarm Output 3 GND Input 4 Remote Shutdown Input 5 Common Input 6 Bypass Output 7 Battery Low Output 8 UPS ON Output 9 Line Loss Outp...

Страница 34: ... control any UPS on the same LAN no matter how far from the UPSs Installation procedure 1 Go to the website http www ups software download com winpower htm 2 Choose the operation system you need and follow the instruction described on the website to download the software 3 When downloading all required files from the internet enter the serial No 511C1 01220 0100 478DF2A to install the software Whe...

Страница 35: ...y power LED is turned on it shows that the utility power is normal l Inv LED green LED Whenever the INV LED is turned on it shows that the loading current is supplied from utility power or battery via the inverter l Battery LED orange LED Whenever the battery LED is turned on it shows that the loading current is supplied from battery via the inverter l Fault LED red LED Whenever the fault LED is t...

Страница 36: ...erloaded in utility mode and UPS still in INV mode Beep twice every sec 13 overloaded in utility mode and UPS in bypass mode Beep twice every sec 14 Utility power abnormal 15 Overloaded in battery mode Early warning Beep twice every sec 16 Overloaded in battery mode Cut off the output Continuously beep 17 Over temperature Continuously beep 18 Inv abnormal Continuously beep 19 Output short circuite...

Страница 37: ...34 Appendix 3 Back Panel Back View of 1K 1KS Figure 1 Back View of 1K 1KS Back View of 2K S Non CE certified Back View of 2KS CE certified 2K CE certified ...

Страница 38: ...35 Back View of 3K S Non CE certified Back View of 3K S CE certified Back view of 6K Back view of 6KS ...

Страница 39: ...36 Back view of 10K Back view of 10KS ...

Страница 40: ...37 614 06440 10 ...

Отзывы: