9
5. Connection and Operation
6) Turn Off the UPS:
6.1) In Inverter Mode:
Press
“ “
button continuously for more than 1 second to turn off the UPS. Then the
UPS will get into self-test status first. After having finished the self-test, the UPS will
get into bypass mode and the Utility Power LED and Bypass LED will light up. At this
time, the UPS might has output. Disconnect the utility power
to turn off the output.
6.2) In Battery Mode:
Press
“ “
button continuously for more than 1 second to turn off the UPS. Then the
UPS will get into self-test status first. After having finished the self-test, the UPS will
be turned off completely.
7) Audible Alarm Mute Function: If the alarm is too annoying in battery mode, you may
press
“
I
”
button continuously for more than 1 second to clear it. Moreover, the alarm will
be enabled when the battery is low to remind you to shutdown the load soon.
8) Operation Procedure of External Battery for Long Backup time Model (
“
S
”
Model)
The units with CE markings
—
(1) Use the battery pack with voltage: 36VDC for 1KS (3 pcs of 12V batteries), 96VDC
for 2KS/ 3KS (8 pcs of 12V batteries). Connection of batteries more than or less than
required will cause abnormality
(2) One end of the external battery cord is a plug for connecting the UPS and the other
end has a plug for connecting the user battery cabinet
(3) Do not connect the UPS to any load yet. Then, connect the power cord of the UPS to
supply utility power to the UPS to make the UPS operate in utility power mode.
(4) Connect the plug of the external battery cord to the external battery socket on the
rear panel of the UPS to complete the connection procedure and the UPS will start
to charge the battery pack.
The unit without CE markings
—
(1) Use the battery pack with voltage: 36Vdc for 1 KS (3 pcs of 12V batteries), 96Vdc for 2
KS/ 3 KS (8 pcs of 12V batteries). Connection of batteries more than or less than
required will cause abnormality.
(2) One end of the external battery cord is a plug for connecting the UPS and the other end
has 3 (or 2) open wires for connecting the battery pack.
(3) The battery connection procedure is very important. Any incompliance may result in the
risk of electric shock. Therefore, the following steps must be strictly complied with.
(4) First connect in series the batteries of the pack to ensure proper battery voltage.
(5) Connect the external battery cord to the battery terminal (DO NOT connect the battery
socket of the UPS first. Otherwise, it may cause electric shock). Connect the red wire
to.