3
STORAGE
When the UPS is not used within seven days of delivery, please pay special attention to the storage requirements.
If the batteries or the equipment is to be stored, they must be kept in a
clean, dry environment and away from extremes of
temperature
.
STORAGE DATA
Storage temperature range: -4
°
F (-20
°
C) to 140
°
F (60
°
C); however, batteries should not be exposed to temperature above 77
°
F
(25
°
C). Each increment of 15
°
F (8
°
C) above 77
°
F (25
°
C) reduces the expected battery life by 50%. See battery manufacturer’s
recommendations.
The ideal environmental temperature range is 59° F to 77° F due to the battery life design at 77 F. Each increment of 15 °F
above 77 °F reduces the expected battery life by 50%.
See battery manufacturer’s recommendations.
UPS without
batteries
-4
°
F to 140
°
F (-20
°
C to 60
°
C)
Relative humidity from 0% to 95%
U N L E S S B A T T E R Y M A N U F A C T U R E R ’ S S P E C I F I C A T I O N S T A T E S
O T H E R W I S E