12-1
12. ALARM OUTPUT
Alarm output is an option. Program [output number] on every alarm point in the [programming alarm
output number] of [alarms] programming.
1. Alarm output
When alarm is on, the terminals of N.O and COM
of alarm output terminals (output number)
specified are shorted as an alarm output. The
instrument delivered is with the alarm output
(MOS relay, mechanical relay 'a' contact or
mechanical relay 'c' contact*) specified.
*Not conforming to international safety
standards.
2. Programming alarm
For programming [alarms], refer to par. 11.5 (Page 11.8) and for programming [alarm output], refer to the
programming flow chart (Page 11.10). The default is [0] - no output. By pressing key after
[programming alarm types], the cursor shifts to output number for programming output number.
The cursor shifts to output number by
pressing key by selecting alarm type.
In case of standard specifications (no alarm
output), [0] is fixed and the cursor shifts to
alarm value.
Program output number from 0 to 6. The
figure shows programming [2]. Program [0] if
no output is necessary.
After on this point or for programming before
[selecting alarm types], refer to the flow chart
of Page 11-10.
MOS relay
Mechanical
relay 'a' contact
Mechanical
relay 'c' contact
N.O N.O
COM
COM N.C
Arrangement of alarm output terminals
[Selecting alarm type]
Alarm types
[Programming
output number]
,
[Programming
alarm value]
(several times)
Output number
Alarm value
~
,
Various keys
All alarm points are number of channels
×
number of levels (4).
As the alarm output points are 6 points and
all alarm points can not be allocated 1:1.
Use output number commonly (OR output).
Number of alarm point and
number of output point
Reference 1
Multiple alarm outputs can be allocated to
one alarm output number. If alarm is on at
any alarm point, alarm is outputted at the
output number.
OR output
Reference 2
Refer to par. 4.5.
Connection of alarm output
terminals
Reference 3
Refer to par. 17.4.
Check of alarm output terminals
Reference 4