CG Drives & Automation, 01-5980-01r2
Functionality
79
PTC Inputs [2332]
Two additional PTC option inputs can be handled. The
settings are therefore “PB-PTC” for the on-board PTC, “PB-
PTC&Opt1”, and “PB-PTC&Opt1-2”.
Start Limitation [234]
The start limitation could be used to protect the motor by
limiting the numbers of starts per hour or securing a
minimum time delay between starts.
A start limitation alarm can only be reset when the alarm
condition is gone.
The actual time left until the next start is allowed is shown in
the status menu [72G] “Time to Next Start”.
Start Limitation Alarm Action [2341]
Start limitation is enabled in this menu by choosing a proper
alarm action, used as thermal protection for the motor.
Autoreset is available for all start limitation alarms, menu
[2552].
Number of starts per hour [2342]
In this menu the allowed number of starts per hour can be
set. If this number is exceeded, an alarm occurs and the
action chosen in menu [2341] is performed.
The alarm is active until the hour has expired. After reset a
new start is allowed. The first hour is counted directly from
the first start of the motor, whereas the following hour is
counted not directly, but from the moment a new start is
done, i.e. no rolling hour.
Minimum time between starts [2343]
In this menu a minimum time between consecutive starts can
be set. If a new start attempt is made before the minimum
time is expired an alarm will occur and the action chosen in
menu [2341] is performed. It is not possible to reset the
alarm until the chosen minimum time has expired and a new
start is allowed.
Time to next start [2344]
In this menu the time to the next allowed start is shown.
Counts down from set value in menu [2343].
Default:
PB-PTC
PB-PTC
0
On-board power board PTC used for
protection, terminal 69 and 70
PB-PTC
&Opt1
1
PB-PTC and PTC input on option B1 used
for protection
PB-PTC
&Opt1-2
2
PB-PTC and PTC input on options B1 and
B2 used for protection
Default:
No action
No action
0
For a definition, see Table 23, page 55
Hard Trip
1
Warning
4
2332 PTC Inputs
Stp
M1:
PB-PTC
2341 StartLim AA
Stp
No action
Default:
10
Range:
1 - 99
Default:
Off
Range:
1 - 60 min
Read only
Unit
minutes
Resolution:
1 min
2342 Starts/h
Stp
M1:
10
2343 MinTBtwStrt
Stp
M1:
Off
2344 TimTNxtStrt
Stp
M1:
min
Содержание emotron TSA Series
Страница 1: ...Emotron TSA Softstarter Instruction manual English Valid from Software version 1 27...
Страница 2: ......
Страница 4: ......
Страница 6: ...2 CG Drives Automation 01 5980 01r2...
Страница 12: ...8 Introduction CG Drives Automation 01 5980 01r2...
Страница 18: ...14 Mounting CG Drives Automation 01 5980 01r2...
Страница 42: ...38 Application guidelines CG Drives Automation 01 5980 01r2...
Страница 46: ...42 Getting started CG Drives Automation 01 5980 01r2...
Страница 70: ...66 Main features CG Drives Automation 01 5980 01r2...
Страница 142: ...138 Functionality CG Drives Automation 01 5980 01r2...
Страница 158: ...154 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5980 01r2...
Страница 160: ...156 Options CG Drives Automation 01 5980 01r2...
Страница 168: ...164 Technical data CG Drives Automation 01 5980 01r2...
Страница 202: ...CG Drives Automation 01 5980 01r2 198...
Страница 203: ......