![CG emotron TSA Series Скачать руководство пользователя страница 122](http://html1.mh-extra.com/html/cg/emotron-tsa-series/emotron-tsa-series_instruction-manual_2585387122.webp)
118
Functionality
CG Drives & Automation, 01-5980-01r2
Analogue Comparator 1,
Level High [6112]
Sets the analogue comparator high level, with range
according to the selected value in menu [6111].
Example
This example describes, both for hysteresis and window type
comparators, the normal use of the constant level high and
low. The function is used for temperature control. Follow the
step by step explanation in Table 31 and Table 32.
Fig. 67
Default:
30.0
Range:
1=1 W, 0.1 A, 0.1 V, 1%, 0.1°C, 1 kWh, 1h,
or 0.001 in [322]
Menu
Function
Setting
325
Process Max
Temperature: 100°C
6111 CA1 Value
PT100_1 (°C)
6112 CA1
Level
HI
50°C
6113 CA1
Level
LO
40°C
6114
CA1 Type
Window
6112 CA1
LevelHI
Stp
30.0
Max
Temp.
50°C
40°C
CA1 Level HI
CA1 Level LO
CA1 output
High
Low
High
Low
Hysteresis
Window
Hysteresis/
window band
Table 31
Comments to Fig. 67 regarding “Hysteresis”
selection.
No.
Description
Hysteresis
1
The reference signal passes the Level LO
value from below (positive edge), the
comparator CA1 does not change, output
stays low.
2
The reference signal passes the Level HI
value from below (positive edge), the
comparator CA1 output is set high.
3
The reference signal passes the Level HI
value from above (negative edge), the
comparator CA1 does not change, output
stays high.
4
The reference signal passes the Level LO
value from above (negative edge), the
comparator CA1 is reset, output is set low.
5
The reference signal passes the Level LO
value from below (positive edge), the
comparator CA1 does not change, output
stays low.
6
The reference signal passes the Level HI
value from below (positive edge), the
comparator CA1 output is set high.
7
The reference signal passes the Level HI
value from above (negative edge), the
comparator CA1 does not change, output
stays high.
8
The reference signal passes the Level LO
value from above (negative edge), the
comparator CA1 is reset, output is set low.
Содержание emotron TSA Series
Страница 1: ...Emotron TSA Softstarter Instruction manual English Valid from Software version 1 27...
Страница 2: ......
Страница 4: ......
Страница 6: ...2 CG Drives Automation 01 5980 01r2...
Страница 12: ...8 Introduction CG Drives Automation 01 5980 01r2...
Страница 18: ...14 Mounting CG Drives Automation 01 5980 01r2...
Страница 42: ...38 Application guidelines CG Drives Automation 01 5980 01r2...
Страница 46: ...42 Getting started CG Drives Automation 01 5980 01r2...
Страница 70: ...66 Main features CG Drives Automation 01 5980 01r2...
Страница 142: ...138 Functionality CG Drives Automation 01 5980 01r2...
Страница 158: ...154 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5980 01r2...
Страница 160: ...156 Options CG Drives Automation 01 5980 01r2...
Страница 168: ...164 Technical data CG Drives Automation 01 5980 01r2...
Страница 202: ...CG Drives Automation 01 5980 01r2 198...
Страница 203: ......