100
Functionality
CG Drives & Automation, 01-5980-01r2
Minimum Pre-Alarm [413]
These menus contain the settings for the load monitor
minimum pre-alarm.
Minimum Pre-Alarm Action [4131]
Setting of the alarm behaviour when a “Minimum Pre-
Alarm” has been detected.
Minimum Pre-Alarm Level [4132]
The value of the minimum pre-alarm level is given as a
percentage of the nominal motor power [223]. When the
actual shaft power (shown within brackets in the display) falls
to a value below this level, the “Minimum Pre-Alarm Delay”
timer, menu [4133], will start counting down. When the
delay time has elapsed, an alarm will be generated according
to the selected “Minimum Pre-Alarm Action” in menu
[4131].
This menu can be set manually to the required alarm level, or
it can be set indirectly, by performing an “Autoset”. See
further information in Fig. 40, page 57.
Example:
The “Min Pre-Alarm Level” is set to 40%. This means that
when the shaft power falls to a value below 40% of the
nominal motor power, the alarm delay timer starts counting
down.
Minimum Pre-Alarm Delay [4133]
When the load level falls below the alarm level for a
continuous period longer than the set “Min Pre-Alarm
Delay” time, the selected “Minimum Pre-Alarm Action” in
menu [4131] is activated..
Minimum Alarm [414]
These menus contain the settings for the load monitor
minimum alarm.
Minimum Alarm Action [4141]
Setting of the alarm behaviour when a “Minimum Alarm”
has been detected.
Minimum Alarm Level [4142]
The value of the minimum alarm level is given as a
percentage of the nominal motor power [223]. When the
actual shaft power (shown within brackets in the display) falls
to a value below this level, the “Minimum Alarm Delay”
timer, menu [4143], will start counting down. When the
delay time has elapsed, an alarm will be generated according
to the selected “Minimum Alarm Action” in menu [4141].
This menu can be set manually to the required alarm level, or
it can be set indirectly, by performing an “Autoset”. See
further information in Fig. 40, page 57.
Default:
No Action
No Action 0
For a definition, see Table 23, page 55.
Hard Trip
1
Soft Trip
3
Warning
4
Default:
92%
Range:
0 - 200% of nominal motor power [223]
4131 MinPreAlAct
Stp
No Action
4132 MinPreAlLev
Run
(
P
shaft
%)
92%
Default:
0.5 s
Range:
0.1–90 s
Default:
No Action
No Action 0
For a definition, see Table 23, page 55.
Hard Trip
1
Soft Trip
3
Warning
4
Default:
84%
Range:
0 - 200% of nominal motor power [223]
4133 MinPreAlDel
Stp
0.5s
4141 MinAlarmAct
Stp
No Action
4142 MinAlarmLev
Run
(
P
shaft
%)
84%
Содержание emotron TSA Series
Страница 1: ...Emotron TSA Softstarter Instruction manual English Valid from Software version 1 27...
Страница 2: ......
Страница 4: ......
Страница 6: ...2 CG Drives Automation 01 5980 01r2...
Страница 12: ...8 Introduction CG Drives Automation 01 5980 01r2...
Страница 18: ...14 Mounting CG Drives Automation 01 5980 01r2...
Страница 42: ...38 Application guidelines CG Drives Automation 01 5980 01r2...
Страница 46: ...42 Getting started CG Drives Automation 01 5980 01r2...
Страница 70: ...66 Main features CG Drives Automation 01 5980 01r2...
Страница 142: ...138 Functionality CG Drives Automation 01 5980 01r2...
Страница 158: ...154 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5980 01r2...
Страница 160: ...156 Options CG Drives Automation 01 5980 01r2...
Страница 168: ...164 Technical data CG Drives Automation 01 5980 01r2...
Страница 202: ...CG Drives Automation 01 5980 01r2 198...
Страница 203: ......