Functionality
129
Clock 1 Weekday [6615]
Weekdays when the clock function is active. Having entered
the editing mode, select or unselect the desired weekdays
with the cursor using the PREV and NEXT keys on the
control panel. Confirm by pressing ENTER. Exit the editing
mode and the activated weekdays will be viewed in the menu
display. The deactivated weekdays are replaced by a dash
mark “-” (e.g. “MTWTF - -”).
Example 1:
The output CLK1 shall be active Mondays to Fridays on
working hours, e.g. 08:00-17:00. This signal is used to start
e.g. a fan with virtual I/O.
Example 2:
The output CLK1 shall be active on weekends, all day.
Clock 2 [662]
Refer to the description for Clock 1 [661].
8.7
Operation/Status [700]
Menu with parameters for viewing all actual operational data,
such as speed, torque, power, etc.
8.7.1
Operation values [710]
Process Value [711]
This menu displays the actual value of the active process
signal, i.e. the same value as in menu [310].
Torque [713]-[714]
These menus displays the actual shaft torque, expressed with
different units in the two menus:
Shaft power [715]- [716]
These menus displays the actual shaft power, expressed with
different units in the two menus:
Default:
2013-01-01
Range:
YYYY-MM-DD
Default:
MTWTFSS (all activated)
Range:
Monday, Tuesday, Wednesday, Thursday,
Friday, Saturday, Sunday.
NOTE: Please make sure that the correct time and date
settings are done for the real time clock, menu group
[740] “Clock”.
Menu
Text
Setting
6611
Clk1TimeOn
08:00
6612
Clk1TimeOff
17:00
6613
Clk1DateOn
2013-02-01 (date in the past)
6614
Clk1DateOff
2099-12-31 (Date in the future)
6615
Clk1Weekday
MTWTF- -
561
VIO 1 Dest
Run FWD
562
VIO 1 Source
Clk1
Menu
Text
Setting
6611
Clk1TimeOn
0:00:00
6612
Clk1TimeOff
23:59:59
6613
Clk1DateOn
2013-02-01 (date in the past)
6614
Clk1DateOff
2099-12-31 (Date in the future)
6615
Clk1Weekday
- - - - - SS
561
VIO 1 Dest
Run FWD
562
VIO 1 Source
Clk1
6614 Clk1DateOff
Stp
2013-01-01
6615 Clk1Weekday
Stp
MTWTFSS
Read-only
Unit
Depends on selected process unit [322].
Resolution
Speed: 1 rpm, 4 digits
Other units: 3 digits
Read-only
Unit:
Nm
Resolution:
0.1 Nm
Read-only
Unit:
%
Resolution:
1 %
Read-only
Unit:
W
Resolution:
1W
Read-only
Unit:
%
Resolution:
1%
711 Process Val
Stp
713 Torque
Stp 0.0Nm
714 Torque
Stp %
715 Shaft Power
Stp
0W
716 Shaft Power
Stp
%
Содержание emotron TSA Series
Страница 1: ...Emotron TSA Softstarter Instruction manual English Valid from Software version 1 27...
Страница 2: ......
Страница 4: ......
Страница 6: ...2 CG Drives Automation 01 5980 01r2...
Страница 12: ...8 Introduction CG Drives Automation 01 5980 01r2...
Страница 18: ...14 Mounting CG Drives Automation 01 5980 01r2...
Страница 42: ...38 Application guidelines CG Drives Automation 01 5980 01r2...
Страница 46: ...42 Getting started CG Drives Automation 01 5980 01r2...
Страница 70: ...66 Main features CG Drives Automation 01 5980 01r2...
Страница 142: ...138 Functionality CG Drives Automation 01 5980 01r2...
Страница 158: ...154 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5980 01r2...
Страница 160: ...156 Options CG Drives Automation 01 5980 01r2...
Страница 168: ...164 Technical data CG Drives Automation 01 5980 01r2...
Страница 202: ...CG Drives Automation 01 5980 01r2 198...
Страница 203: ......