122
Functionality
CG Drives & Automation, 01-5980-01r2
(CA1&F1)+(T1Q&!A2)
With the above values inserted the resulting logic expression
now becomes:
which is equal to 1.
Logic 1 Input 1 [6212]
In this menu the first input for the Logic 1 function is
selected. The same selections are valid for [6214] L1 Input 2,
[6216] L1 Input 3, and [6218] L1 Input 4.
This table is also valid for the input signals in logic functions
2 [622], 3 [623], and 4 [624], however default values vary.
See Menu List in Appendix 1.
Note that a logic function can not directly use itself as an
input signal, e.g. for the L1 Input, it will not be possible to
choose L1 or !L1.
Logic 1 Operator 1 [6213]
In this menu the first operator for the Logic 1 function is
selected.
Default:
CA1
CA1
0
Analogue comparator 1 output.
!A1
1
Analogue comp 1 inverted output.
CA2
2
Analogue comparator 2 output.
!A2
3
Analogue comp 2 inverted output.
CA3
4
Analogue comparator 3 output.
!A3
5
Analogue comp 3 inverted output.
CA4
6
Analogue comparator 4 output.
!A4
7
Analogue comp 4 inverted output.
CD1
8
Digital comparator 1 output.
!D1
9
Digital comp 1 inverted output.
CD2
10
Digital comparator 2 output.
!D2
11
Digital comp 2 inverted output.
CD3
12
Digital comparator 3 output.
!D3
13
Digital comp 3 inverted output.
CD4
14
Digital comparator 4 output.
!D4
15
Digital comp 4 inverted output.
L1
16
Logic output 1.
Not used for Logic 1.
!L1
17
Logic output 1 inverted.
Not used for Logic 1.
L2
18
Logic output 2.
Not used for Logic 2.
!L2
19
Logic output 2 inverted.
Not used for Logic 2.
L3
20
Logic output 3.
Not used for Logic 3.
621 Logic 1
Stp (1&1)+(1&0)
6212 L1 Input 1
Stp
CA1
!L3
21
Logic output 3 inverted.
Not used for Logic 3.
L4
22
Logic output 4.
Not used for Logic 4.
!L4
23
Logic output 4 inverted.
Not used for Logic 4.
T1Q
24
Logic timer 1 output
!T1Q
25
Inverted logic timer 1 output
T2Q
26
Logic timer 2 output
!T2Q
27
Inverted logic timer 2 output
T3Q
28
Logic timer 3 output
!T3Q
29
Inverted logic timer 3 output
T4Q
30
Logic timer 4 output
!T4Q
31
Inverted logic timer 4 output
F1
32
Flip-flop output 1.
!F1
33
Flip-flop output 1 inverted.
F2
34
Flip-flop output 2.
!F2
35
Flip-flop output 2 inverted.
F3
36
Flip-flop output 3.
!F3
37
Flip-flop output 3 inverted.
F4
38
Flip-flop output 4.
!F4
39
Flip-flop output 4 inverted.
CTR1
40
Counter output 1.
!CTR1
41
Counter output 1 inverted.
CTR2
42
Counter 2 output.
!CTR2
43
Counter output 2 inverted.
Default:
&
·
0
When
·
(dot) is selected, the Logic 1
expression is finished (when two or
three expressions are tied together).
&
1
&=AND
+
2
+=OR
^
3
^=EXOR
6213 L1 Op 1
Stp
&
Содержание emotron TSA Series
Страница 1: ...Emotron TSA Softstarter Instruction manual English Valid from Software version 1 27...
Страница 2: ......
Страница 4: ......
Страница 6: ...2 CG Drives Automation 01 5980 01r2...
Страница 12: ...8 Introduction CG Drives Automation 01 5980 01r2...
Страница 18: ...14 Mounting CG Drives Automation 01 5980 01r2...
Страница 42: ...38 Application guidelines CG Drives Automation 01 5980 01r2...
Страница 46: ...42 Getting started CG Drives Automation 01 5980 01r2...
Страница 70: ...66 Main features CG Drives Automation 01 5980 01r2...
Страница 142: ...138 Functionality CG Drives Automation 01 5980 01r2...
Страница 158: ...154 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5980 01r2...
Страница 160: ...156 Options CG Drives Automation 01 5980 01r2...
Страница 168: ...164 Technical data CG Drives Automation 01 5980 01r2...
Страница 202: ...CG Drives Automation 01 5980 01r2 198...
Страница 203: ......