7
Pressure
Ph
High alarm Hst+14
Open
Pressure relief
Valve(s)
Closed Hst+9
Neutral Zone
P1 Stop Hst+7
E
P2 Stop
d
d
P1 ON
E
P2 ON Hst+1
Hst
Pb
Low P alarm Hst-2
SCHEMATIC DIAGRAM MP4N CLOSED TANK
Arrêt P1
SCHEMATIC DIAGRAM MP5N/MP7 CLOSED TANK
On these units, there may be 1 or 2 pressure control valves.
Same principle than open tank system except that the water level is calculated from the water weight inside
the tank. For this, a weight sensor is connected to an electronic card inside the control box. This card power
supplies the weight sensor and acquires its signal, translated into inner water level, replacing the standard
water level sensors.
Pressure
Ph High P alarm Hst+14
Open
Pressure Relief
Valve
Closed Hst+9
Neutral zone
P1 Stop Hst+7
Start Pump
d
P0 Hst+2
Hst
Pb Low P alarm Hst-2