23
TECHNICIAN MENU
This menu allows you to set:
•
Lack of water temporization,
•
Cascade temporization (if 2 pumps)
•
Stopping pumps temporization,
•
Filling tank temporization,
•
Low pressure alarm temporization,
•
Display language,
•
Reading event list,
•
Sensor scale correction
•
Relays tests into Autotest sub-menu
ACTION
DISPLAY
Post lack of water temporization
It is the temporization before activating pump(s) and after a lack of
water default.
Press + or
– to modify the value,
Press yellow
for next line,
NO WATER TEMPORISATION
1 SEC.
Cascade temporization (MP5 / MP7)
Temporization to avoid the 2 pumps starting together
Press + or
– to modify the value,
Press yellow
for next line,
CASCADING TEMPO.
1 SEC.
Stopping pump temporization (MP5/7)
Temporization to avoid stopping the 2 pumps at the same time.
Press + or
– to modify the value,
Press yellow
for next line,
STOP PUMP TEMPO.
1 SEC.
Filling temporization
It is temporization to close the filling electro valve when the correct
water level has been reached inside the tank.
Press + or
– to adjust the value,
Press yellow
for next line,
FILLING TEMPO.
6 SEC.
Low pressure alarm temporization
If the pressure reaches the low alarm level, the alarm relay will only be
powered on after a preset period of time.
Press + or
– to adjust this period,
Press yellow
for next line,
LOW PRESS. TEMPO.
1 SEC.
Pumps cycling
On 2 pumps units, you can set each pump working time P1/P2
Press + or
– to adjust the value,
Press yellow
for next line,
SWAPPING TEMPO.
10 MIN.
NETWORK LEAKAGE parameters
Press + to enter this sub-menu,
Refer to page 24 hereafter,
Press yellow
for next line,
LEAKAGE
DETECTION
Display Language
Choose language used for display.
Press + or
– to select the required language,
Press yellow
for next line,
LANGUAGE
ENGLISH
Pressure recorder parameters
This function is not used. Netherthless, it is possible to make trends or
read values from a BMS using the Modbus optional card CI8021
Press yellow
for next line,
RECORDER
Press :
Yellow
and white
to enter the menu.
Yellow
to get to the next frame/setting,
Yellow
to get to the previous frame/setting.