LEAKAGE DETECTION
This function only applies for modules fitted with a volumetric impulsions counter.
In the Technician menu,
Press + when the message ‘’LEAKAGE DETECTION’’ is displayed to enter this sub-menu.
Impulsion number on 24hrs
If the impulsion number is higher than the set point, we consider there
is a network leakage
Adjustable from 1 to 300 impulsions /24hrs.
Press + or
– to adjust the value, Press yellow
,
PULSES / 24 H
10
ACTION
If a network leakage is detected, you can choose to continue running
(no action) or to stop the pump(s) and close electrovalve.
Press + or
– to adjust the value, Press yellow
,
ACTION
NONE
Enabling / Disabling the function
Press + or
– to Enable or Disable the function,
Press yellow
and save your modifications,
To save follow the instructions below.
DETECTION
DISABLE
SAVE MODIFICATIONS
At any time, you can interrupt the setting procedure and save the
changes by pressing the VALIDATION key.
To save your modifications, Press + for YES and
– for NO.
ANY PARAMETRE MODIFICATION SHOULD BE VALIDATED THIS
WAY
_________________________________________________________________________
IMPORTANT
The NETWORK LEAKAGE function is disabled by default in the factory settings.
__________________________________________________________________________________