17
TROUBLESHOOTING GUIDE
FINDINGS
PROBABLE CAUSE
SOLUTION
Low pressure alarm
Pump(s) stripped
Change
Overflow valve open too wide
Set
Low pressure alarm set point too
high
Set
Pump(s) do not start
Fuse(s) splashed
Replace and control
Set point too high
Set
Relay scratched
Replace
Pump(s) out of order
Replace
Pump No. inversed in 1pump
mode
Set
High pressure alarm
Overflow valve too screwed
Set
Overflow valve fooled or blocked Clean or replace. WARNING:
unscrew the spring before
dismounting
High pressure set point too low
Set
Pump(s) always on
Pump(s) bad drained
Drain
Pump(s) fooled
Clean
Not enough output pressure
Check the quotation
Overflow valve open too wide
Set
Pressure set point too high
Set
Too high differential value
Set (Standard value=0.5)
Network leakage
Check
Setting tee closed
Open 1 turn
Lack of water default
Level sensor incorrectly placed
(open tank only)
Modify and set (12cm)
Level sensors out of order (open
tank only)
Replace
Bad calibration of the zero weight
(closed tank only)
Check weight calibration in this
users’ manual
Cold water valve closed
Check or open
Electrovalve or relay out of order Replace