Chapter 6 - Parameter Description
6-32
The VFD display will show LOR fault at com. loss.
I/O-94
setting is for communication using RS232-
RS485 converter and should be set according to
converter specification. This time setting creates a
delay before VFD sends response.
$ )57+
"
! "
"
1
The digital input N.O. type can be changed to N.C.
in I/O-95 by setting a corresponding bit to 1. The
below table shows the digital inputs bit mapping.
Input P6 P5 P4 M8 M7 M6 M5 M4 M3 M2 M1
bit
10 9
8
7
6
5
4
3
2
1
0
N.O.
0
0
0
0
0
0
0
0
0
0
0
N.C.
1
1
1
1
1
1
1
1
1
1
1
$ )536 54+
" & ", "
! !
" '"
The VFD can monitor motor temperature with
thermistor PTC (positive temperature coefficient)
or NTC (negative temperature coefficient) sensor
connected to NT or NE and 5G terminal.
I/O-97
has three bits for motor overheat protection
selection. Second bit is not active and reserved for
future use. There are following possible
combinations for this parameter:
01
0
, 00
0
or 11
0
- The Motor Overheat protection is
disabled.
01
1
or 00
1
- The Motor Overheat protection is
enabled with PTC thermistor sensor.
1
1
1
or
1
0
1
- The Motor Overheat protection is
enabled with NTC thermistor sensor.
The thermistor rating ±5%
at 25°C is for PTC 1k
and for NTC 2.545k . The temperature range is for
PTC 0-125°C and for NTC 0-150°C.
I/O-98
is the motor overheat temperature setting in
Celsius. The VFD will trip when motor temperature
exceeds the I/O-98 value.
I/O In No/NC Set
95 00000000000
I/O OH Trip Sel
97
010
I/O MO Trip Temp
98
110°C
Содержание CI-007-P2
Страница 23: ......
Страница 107: ......
Страница 109: ...Chapter 6 Parameter Description 7 2 7 3 PID control Sleep mode with Sleep Pressure Boost function diagram...
Страница 110: ...Chapter 6 Parameter Description 7 4 PID control with Pipe Broken function diagram...
Страница 111: ...Chapter 6 Parameter Description 7 4 7 5 PID control with Pre PID function diagram...
Страница 112: ...Chapter 6 Parameter Description 7 5 7 6 PID Control Setting Notes...
Страница 113: ......
Страница 126: ...Chapter 9 Options 9 7 Conduit box for 030 040HP VFD Conduit box for 050 075HP VFD Conduit box for 100 125HP VFD...