Chapter 5 – Parameter List
5-8
FG1-58
933A
No Motor Trip Current Level
NoMotorLevel
5 to 100 [%]
FG1-59
933B
No Motor Trip Time Setting
NoMotorTime
0.1 to 10.0 [Sec]
FG1-60
933C
Electronic Motor Overload
ETH Select
0 (No)
1 (Yes)
FG1-61
933D
Electronic Thermal Level for 1
Minute
ETH 1min
FG1-62 to 200 [%]
FG1-62
933E
Electronic Thermal Level for
Continuous
ETH Cont
50 to FG1-61[%]
(Maximum 200%)
FG1-63
933F
Motor Cooling Type Selection
Motor Type
0 (Self-cool)
6-16
1 (Forced-cool)
FG1-64
9340
Overload Warning Level
OL Level
30 to 110 [%]
FG1-65
9341
Overload Warning Time
OL Time
0.0 to 30.0 [sec]
FG1-66
9342
Overload Trip Selection
OLT Select
0 (No)
1 (Yes)
FG1-67
9343
Overload Trip Level
OLT Level
30 to 150 [%]
FG1-68
9344
Overload Trip Delay Time
OLT Time
0.0 to 60.0 [sec]
FG1-69
9345
Input/Output Phase Loss
Protection
Trip Select
000 to 111 (Bit Set)
FG1-70
9346
Stall Prevention Mode Selection
Stall Mode
0 (No)
1 (Yes)
FG1-71
9347
Stall Prevention Level
Stall Level
30 to 200 [%]
FG1-72
9348
Accel/Decel Change Frequency
Acc/Dec Ch F
0.00 to FG1-30 [Hz]
6-17
FG1-73
9349
Reference Range for Accel/Decel
Acc/Dec Freq
0 (Max freq)
1 (Delta freq)
FG1-74
934A
Accel/Decel Time Scale
Time Scale
0 (0.01 sec)
6-17
1 (0.1 sec)
2 (1 sec)
FG1-81
9351
Start Delay time after Run
Command is activated
Run Delay T
0 to 6000 sec
FG1-90
935A
Up/Down Save Mode
UpDnSaveMode
0 (No)
1 (Yes)
FG1-91
935B
Up/Down Save Freq
xx.xxHz
0.00 to FG1-30 [Hz]
Display
5.6 [FG1] Parameter Group Default Settings
CODE
LCD Keypad
Display
Basic
Supply
Fan
Exhaust
Fan
Cooling
Tower
Circul.
Pump
Subm.
Pump
Vacuum
Pump
Const.
Torq.
FG1-00 Jump Code
70
70
70
70
70
70
70
70
FG1-02 Acc. Pattern
(Linear)
(Linear)
(Linear)
(Linear)
(Linear)
(Linear)
(Linear)
(Linear)
FG1-03 Dec. Pattern
(Linear)
(Linear)
(Linear)
(Linear)
(Linear)
(Linear)
(Linear)
(Linear)
FG1-04 Start Curve
50 [%]
50 [%]
50 [%]
50 [%]
50 [%]
50 [%]
50 [%]
50 [%]
FG1-05 End Curve
50 [%]
50 [%]
50 [%]
50 [%]
50 [%]
50 [%]
50 [%]
50 [%]
FG1-10 PreHeat Mode
(No)
(No)
(No)
(No)
(No)
(No)
(No)
(No)
FG1-11 PreHeatLevel
20 (%)
20 (%)
20 (%)
20 (%)
20 (%)
20 (%)
20 (%)
20 (%)
FG1-12 PreHeatDuty
30 (%)
30 (%)
30 (%)
30 (%)
30 (%)
30 (%)
30 (%)
30 (%)
FG1-20 Start Mode
Accel
Accel
Accel
Accel
Accel
Accel
Accel
Accel
FG1-21 DcSt Time
0.0 [sec]
0.0 [sec]
0.0 [sec]
0.0 [sec]
0.0 [sec]
0.0 [sec]
0.0 [sec]
0.0 [sec]
FG1-22 DcSt Value
50 [%]
50 [%]
50 [%]
50 [%]
50 [%]
50 [%]
50 [%]
50 [%]
FG1-24 DcBr Delay
0.1 [sec]
0.1 [sec]
0.1 [sec]
0.1 [sec]
0.1 [sec]
0.1 [sec]
0.1 [sec]
0.1 [sec]
FG1-25 DcBr Freq
20.00 [Hz] 20.00 [Hz]
20.00 [Hz]
20.00 [Hz]
20.00 [Hz]
20.00 [Hz]
20.00 [Hz]
20.00 [Hz]
FG1-26 DcBr Time
3.0 [sec]
3.0 [sec]
3.0 [sec]
3.0 [sec]
3.0 [sec]
3.0 [sec]
3.0 [sec]
3.0 [sec]
Содержание CI-007-P2
Страница 23: ......
Страница 107: ......
Страница 109: ...Chapter 6 Parameter Description 7 2 7 3 PID control Sleep mode with Sleep Pressure Boost function diagram...
Страница 110: ...Chapter 6 Parameter Description 7 4 PID control with Pipe Broken function diagram...
Страница 111: ...Chapter 6 Parameter Description 7 4 7 5 PID control with Pre PID function diagram...
Страница 112: ...Chapter 6 Parameter Description 7 5 7 6 PID Control Setting Notes...
Страница 113: ......
Страница 126: ...Chapter 9 Options 9 7 Conduit box for 030 040HP VFD Conduit box for 050 075HP VFD Conduit box for 100 125HP VFD...