![CERUS CI-007-P2 Скачать руководство пользователя страница 63](http://html1.mh-extra.com/html/cerus/ci-007-p2/ci-007-p2_installation-programming-operation-and-maintenance-manual_2583979063.webp)
Chapter 5 – Parameter List
5-20
CODE
Comm.
Addr
Description
LCD Keypad
Display
Setting Range
Run
Adj.
Page
APP-68
9644
Auto Change Level
AutoEx Level
FG-32 to FG1-30 [Hz]
6-35
APP-69
9645
Inter-Lock Selection
Interlock
0 (No)
1 (Yes)
APP-78
964E
Ext PID Operation Selection
Ext PI Mode
0 (No)
1 (Yes)
APP-79 964F
Ext PID Reference Signal Selection Ext Ref Sel
0 (I)
1 (V1)
2 (Pulse)
3 (Key-Pad)
APP-80
9650
Ext PID Set Point
Ext SetPoint
0.0 to 3000.0 [Unit]
APP-81
9651
Ext PID Feedback Signal Selection Ext Fbk Sel
0 (I)
1 (V1)
2 (Pulse)
APP-82
9652
Ext PID Feedback Unit Select
ExtFbk Unit
PSI, °F, °C, inWC,
inM, Bar, mBar, Pa,
kPa, CUST
APP-84
9654
Ext PID Fdbk Unit Max Value
ExtFbk UnitH
0.0 to 3000.0 [Unit]
APP-85
9655
P Gain for ExtPID
ExtPID PGain
0.0 to 999.9 [%]
APP-86
9656
I Time for ExtPID
ExtPID ITime
0.0 to 32.0 [sec]
APP-87
9657
D Time for ExtPID
ExtPID DTime
0 to 2000 [msec]
APP-88
9658
High Limit Frequency for ExtPID
Control
ExtPID Lmt H
0.00 to 100.00 [%]
APP-89
9659
Low Limit Frequency for ExtPID
Control
ExtPID Lmt L
0.00 to 30.00 [%]
APP-90
965A
ExtPID Output Scale
ExtPID Scale
0.0 to 999.9
6-36
APP-91
965B
ExtPID P2 Gain
Ext P2 Gain
0.0 to 999.9
APP-92
965C
ExtPID P Gain Scale
Ext P Scale
0.0 to 100.0
APP-93
965D
ExtPID F Gain
ExtPID FGain
0.0 to 999.9 [%]
APP-95
965F
ExtPID Output Inverse
ExtPIDOutInv
0 (No)
1 (Yes)
APP-97
9661
ExtPID Loop Time
ExtPIDLoopT
50 to 200 [msec]
Содержание CI-007-P2
Страница 23: ......
Страница 107: ......
Страница 109: ...Chapter 6 Parameter Description 7 2 7 3 PID control Sleep mode with Sleep Pressure Boost function diagram...
Страница 110: ...Chapter 6 Parameter Description 7 4 PID control with Pipe Broken function diagram...
Страница 111: ...Chapter 6 Parameter Description 7 4 7 5 PID control with Pre PID function diagram...
Страница 112: ...Chapter 6 Parameter Description 7 5 7 6 PID Control Setting Notes...
Страница 113: ......
Страница 126: ...Chapter 9 Options 9 7 Conduit box for 030 040HP VFD Conduit box for 050 075HP VFD Conduit box for 100 125HP VFD...