page 25
www.CentSys.com
Control
box
Mains
isolator
switch
9
5
9
6
6
10
1
2
3
8
4
7
FIGURE 16. CABLING REQUIREMENTS
Control
box
350mm
cable loop
Mains
isolator
switch
9
5
9
6
6
10
1
2
3
8
4
7
7. Cabling Requirements
S
ECTION
7
CABLING
REQUIREMENTS
Legend
1. 90V - 240V AC Mains cable via Mains isolator
1
switch (3 core LNE 0,5mm
2
)
2
,
or low-voltage 16V AC battery charger supply
3
(2 core 1,5mm²).
2. Intercom cable (n1 + 6 core) to house.
3. Master Motor (MTR M) or Slave Motor (MTR S) cable.
(Minimum, 2 core 1.5mm
2
+ 4 core 0,22mm
2
multi-stranded)
4
.
4. Optional radio receiver cable (3 core 0,5mm
2
multi-stranded, optional)
5
.
5. Optional Pedestrian Keyswitch (2 core 0,5mm
2
multi-stranded) or optional keypad
(3 core 0,5mm
2
multi-stranded).
6. Optional, but recommended infrared Safety Beams (3 core 0,5mm
2
multi-stranded
or 4 core 0.5mm
2
for CE compliance).
7. Optional intercom cable (n2+2 core 0,5mm
2
multi-stranded) to gate station.
8. Optional electric lock (2 core 0.5mm
2
).
9. Optional Pillar Light cable (3 core, size according to power regulations).
10. Optional ground loop for free-exit (1 core 0.5mm
2
multi-stranded - silicone-coated)
6
.
•
All cables must be routed in conduit unless underground cable is
being used
•
Mains isolator must be less than one metre from the operator
•
Safety Beams are always recommended, i5 or Photon
1.
Mains isolator supplied with V-Series wall box
2. Increase cable thickness if Pillar Lights are to be installed
3. Screened cable is always recommended to provide better protection against lightning - earth one end of screening
4. Please use V-Series cabling. Order reference: CABLEVEC68
5. For optimum range an external receiver can be mounted on the wall
6. Consult manufacturer of loop detector for specific details