Table of resistances
-20
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105
110
115
120
125
130
48.535
36.465
27.665
21.158
16.325
12.694
9.950
7.854
6.245
5.000
4.028
3.266
2.663
2.184
1.801
1.493
1.244
1.041
876
740,7
629,0
536,2
458,8
394,3
340,0
294,3
255,6
222,7
190,7
170,8
150,5
Temperature (°C)
Resistance (
W
)
Measuring range from -20 to +130°C
Used as:
Boiler temperature sensor, DHW tank sensor,
Return flow temperature sensor, Main flow temperature sensor
13.2 TABLE OF RESISTANCES OF NTC 5K/25°C SENSOR