4.0. HISTORY
History
E
- conditions that result the shutdown of the boiler. The error must be rectified before the next
boiler starts.
Error list / warnings used in order to have an insight into the errors / warnings that
have occurred. Written is: time of occurrence errors / warnings, error code / warning;
description of the error / warning. The first press on the field error / warning field error
/ warnings is indicated, in addition to see and date generated errors / warnings.The
second press on the selected error / warning, prints a detailed description of the error
/ warnings and corrective action errors / warnings.
ERROR
NAME
DESCRIPTION
E1
Boiler status:
Boiler go to phases
S7, C0
and
OFF.
Possible causes
:
Interruption on el. connections between
sensor and boiler, connection to the boiler, cold
connection or DHW sensor is invalid.
DHW sensor error
E2
Boiler status:
Boiler go to phases
S7, C0
and
OFF.
Possible causes
:
Interruption on el. connections between
sensor and boiler, cold connection or buffer tank sensor (up)
is invalid.
Buffer tank sensor error
(Up)
E3
Boiler status:
Boiler go to phases
S7, C0
and
OFF.
Possible causes
:
Interruption on el. connections between
sensor and boiler, cold connection or buffer tank sensor
(down) is invalid.
Buffer tank sensor error
(Down)
E4
Boiler status:
Boiler go to phases
S7, C0
and
OFF.
Possible causes:
Interruption on el. connections between
sensor and boiler, cold connection or invalid flue gas
sensor.
Flue gas sensor error
E5
Boiler status
:
Boiler work normally, problem appears on
work of CM2K-P regulator if is installed.
Possible causes:
Interruption on el. connections between
sensor and boiler, cold connection or invalid outside
temperature sensor.
Outside temperature
sensor error
E6
Possible causes
:
Interruption on el. connections between
sensor and boiler, cold connection or invalid main flow
sensor.
Main flow sensor error
E7
Boiler status:
Boiler go to phases
S7, C0
and
OFF.
Possible causes
:
Interruption on el. connections between
sensor and boiler, connection to the boiler, cold connection
or invalid return flow sensor.
Return flow sensor error
E8
Boiler status:
Staying in phase OFF (can be appear in OFF
phase because of bimetal sensor information about too
high temperature).
Possible causes:
Feeding tube temperature is higher than
80°C, interruption on el. connections between bimetal
sensor and boiler, connection to boiler, cold connection or
invalid bimetal sensor.
Pellet supply tube
temperature too high
Technical instructions REGULATION