background image

 

CellarMate Manual 

 

 

Page 3 

The LAO will protect the compressor and refrigerant system. It has two distinct components; 
a crankcase heater to keep the oil in the compressor warm and prevent slugging on start-up, 
and a head pressure control to automatically cycle the condenser fan on and off to maintain 
system head pressure. 

To confirm that the system is working, feel the bottom of the heater when the compressor 
unit has cycled off.  When the unit starts, the condenser fan does not start at the same time as 
the compressor.  The condenser fan starts after the head pressure has built up.  As the unit is 
running, the condenser fan cycles off and on while it holds the head pressure within a fixed 
range.  The colder the air, the more frequent the cycling and the longer the duration. 

Humidifier and Humidistat 

A popular option for the CellarMate is the humidifier, supplied with a sheet metal adapter 
box and a pre-wired humidistat.  The humidifier is designed for field installation and can be 
retrofitted onto existing CellarMate units.  Each humidifier model is furnished with an 
electronic digital humidistat to control the humidity in the cellar.  The humidifier mounts 
onto the CellarMate unit using the common drain, and requires a hot water supply.  No 
additional external power is required. 

When the humidistat calls for humidity, a damper inside the enclosure opens and allows air 
from the evaporator fan to flow through the drip pad and back into the inlet of the unit.  A 
solenoid valve also opens, allowing water to flow into the distribution channel and drip down 
over the pad.  The air flowing over the wet pad surface adds moisture to the air and increases 
the humidity in the cellar. 

Since the cellar air temperature is cold, the water entering the humidifier must be HOT to be 
absorbed into the air stream.  To avoid the buildup of dirt on the pad, install a 5 or 10 micron 
inline water filter ahead of the humidifier to keep dirt from fouling the evaporation pad 
inside.  To avoid the buildup of mineral deposits on the pad, install a water softener. 

To insure adequate wetted surfaces and help flush away excess minerals, set the water flow 
to always have a flow of water to the drain.  When operating, the humidifier uses 
approximately 1 to 2 gallons of water per hour.  About 60% of the water passes through and 
goes out the drain.  There is an orifice in the line to restrict the flow of water, but a throttling 
valve may be needed to keep too much water from going to the pad.  All that is needed is a 
steady drip of water out of the drain to ensure adequate wetting and flushing of the pad 
media.  Pipe a gravity drain line to an open floor or sink drain, or use a condensate pump 
where a gravity drain is impractical.  Discharge the excess drain water directly onto the 
ground, or combine the discharge into the condensate drain from the unit, but only 
downstream from the loop trap. 

The CellarMate humidifier uses a 10” wide x 11” high x 2”thick pad.  The rated output 
capacity for wine cellars at 55°F is 1.62.3 gallons per day (gpd) with 760°F water supply, 
34.57 gpd with 950°F water, and 7.45.1 gpd with 120°F water.  Weight of operating 
humidifier is 10 lbs. 

Содержание Wine Cellar Climate Control

Страница 1: ...CellarMate The Key to Wine Cellar Climate Control Installation Operation and Maintenance Manual...

Страница 2: ...te control systems are designed to provide you with many years of reliable maintenance free service Please read the following information especially the safety information to ensure that you receive t...

Страница 3: ...ur CellarMate model Confirmation of Ownership We store model numbers serial numbers and owner information in our archives for ten years In the event of fire flood or theft your registration serves as...

Страница 4: ...8 Air Flow Illustration 8 Planning the Installation 8 Pre installation Checklist 9 Placing the Unit 9 Noise Insulation 9 Grilles 9 Outdoor Installation 10 Mounting the Unit 11 Installing the Condensa...

Страница 5: ...Duct Installation 25 Dual Outlet Duct Installation 25 Wiring Diagram Models 025 and 050 26 Wiring Diagram Models 088 and 200 27 Wiring Diagram Humidifier 28 Troubleshooting 29 Start Up 29 Unit Does No...

Страница 6: ...ed direct drive motors requiring no maintenance All exterior framing of the CellarMate is power coated 0 063 gauge aluminum to prevent rust and corrosion All coils are copper tubes with aluminum fins...

Страница 7: ...is transferred to the water A control valvue is used to regulate the flow of water to maintain head pressure Leaving water is clean and acceptable for other applications This option available for the...

Страница 8: ...oid valve also opens allowing water to flow into the distribution channel and drip down over the pad The air flowing over the wet pad surface adds moisture to the air and increases the humidity in the...

Страница 9: ...n the evaporator coil and the blower and is complete with contactor s and limit controls Electrical Controls The electrical components and controls are located in a separate area accessible through th...

Страница 10: ...See unit dimensions on Page 21 Duct collars Duct collars are available Medium collars are used for top or side duct ports large collars are used for end ports See unit dimensions on Page 21 Cover pla...

Страница 11: ...CellarMate Manual Page 6...

Страница 12: ...etely stopped Fan impellers continue to turn free wheel after the power is turned off Never pressurize equipment above the specified test pressure See Specification Sheet Do not operate near water Do...

Страница 13: ...he fan and UP arrow buttons The unit will run as long as the temperature of the space is above the thermostat set point After several minutes the unit will expel cold air from the evaporator section a...

Страница 14: ...alf Provide a 3 access clearance around the unit for maintenance access If a humidifier is installed leave space in front of it for service access Noise Insulation When placing the CellarMate unit clo...

Страница 15: ...nt the unit above the ground on a solid waterproof base to protect the unit from ground water Keep the area around the unit clean and free of debris It is recommended to double insulate the ducts with...

Страница 16: ...cting To prevent transmitting vibration and noise add thick rubber pads Installing the Condensate Drain Connection The CellarMate dehumidifies the inside of the wine cellar If the wine cellar vapor ba...

Страница 17: ...he plug on the CellarMate Confirm that the wiring and breaker conform to the rated load listed on the serial plate See illustration below Use a dedicated circuit and wiring Do not modify the plug in a...

Страница 18: ...the appropriate color coded slot on the terminal strip and that the connections are secure Mounting the Thermostat Two sets of instructions are provided with the unit the Homeowner s Guide and the Ins...

Страница 19: ...mizes air circulation in the room Avoid short circulating the air To avoid collecting dust do not install the return air registers directly on the floor Avoid placing the supply or return grilles wher...

Страница 20: ...sags or bends Place supports close enough to prevent the flexible ducting from sagging or bending Stretch the duct to create a smooth interior and reduce air resistance Rigid ductwork is best Insert...

Страница 21: ...tall the ductwork from the CellarMate to the wine cellar Connect the supply air ductwork from the cellar to the supply air outlets at the CellarMate unit Connect the return air ductwork from the cella...

Страница 22: ...ication Operating the Unit Listen for the compressor The hum will be audible with no excessive vibration or sounds Initially the unit may run continuously for several hours up to a day or more while i...

Страница 23: ...e temperature in different zones To maintain the same temperature throughout the wine cellar set the thermostat to FAN so the supply fans run continuously while the unit is cooling as opposed to AUTO...

Страница 24: ...e Filters The evaporator and condenser coils are equipped with reusable washable air filters The filters protect the coils from becoming coated or plugged by dust Clean the filters based on the amount...

Страница 25: ...the brush attachment to clean the coils Clean condensate pan under the evaporator coil by flushing Keep the drain pan clear of debris Inspect the cabinet for corrosion or rust Inspect for dirt build...

Страница 26: ...CellarMate Manual Page 21 Dimensions and Components and Components...

Страница 27: ...CellarMate Manual Page 22 Performance and Specifications...

Страница 28: ...al Page 23 Typical Mounting Arrangements The following illustrations are suggested mounting arrangements These illustrations are not intended to be complete and detailed installation drawings Through...

Страница 29: ...CellarMate Manual Page 24 Ducting Options...

Страница 30: ...CellarMate Manual Page 25 Single Outlet Duct Installation Dual Outlet Duct Installation...

Страница 31: ...CellarMate Manual Page 26 Wiring Diagram Models 025 and 050...

Страница 32: ...CellarMate Manual Page 27 Wiring Diagram Models 088 and 200...

Страница 33: ...CellarMate Manual Page 28 Wiring Diagram Humidifier...

Страница 34: ...nes in the Thermostat Installation and Operating Guide Changed settings on the thermostat The internal timer did not complete the timed delay Follow the manufacturer s instructions to override the tim...

Страница 35: ...in the guide Press fan ON switch to check evaporator fan only Compressor not operating High pressure switch open button up Condenser air flow is blocked Remove blockage Clean filter and coil if neede...

Страница 36: ...perature Problems are occurring even though the unit seems to be fully operational evaporator fan blows air into the cellar and compressor and condenser fan runs Cellar Temperature is Too Low Below 51...

Страница 37: ...thout Optional Humidifier Possible Cause Solution Not enough evaporator air flow Remove blockage in supply or return ductwork Check and clean filter and coil Coil frozen shut off unit for two hours De...

Страница 38: ...ot Cooling Possible Cause Solution Compressor Check and reset high limit switch Clear blockage of condenser air flow Ambient temperature above 95 F Humidity Too High When Unit is Not Running Possible...

Страница 39: ...ut the Sound of Unit is Objectionable Possible Cause Solution Noise is from air flow Redirect air flow Add baffles Add insulated ductwork Noise is from unit Add sound baffle between unit and occupied...

Страница 40: ...rty Filters Coils Possible Cause Solution Condenser fan not operating Repair or replace Defective switch Replace Unit Cycles On and Off More than 8 Times Hour Possible Cause Solution Thermostat malfun...

Страница 41: ...any other obligations or liabilities for CellarMate LLC in connection with the sale of its systems Indemnification Purchaser agrees to indemnify hold harmless and defend seller and its officers direct...

Страница 42: ...o gas phase in the coil The evaporation section is connected to or inside the wine cellar Flexible Duct Round ducts with a steel reinforced plastic liner a layer of insulation and an outer plastic lay...

Отзывы: