The remote ON/OFF requires changeover contacts, one input opens as the other close.
If both transitions are not picked up the status is not changed.
Relay characteristics (Remote ON/OFF)
•
Signal voltage
+5 VDC (galvanic insulated)
•
Max wire size
1 mm
2
Functional table for remote ON/OFF function
#
Pin 1-3
Pin 2-3
Status
Indication
1
Open
Open
Normal operation
All (Green)
2
Closed
Open
OFF
AC output (OFF)
AC Input (Green)
DC Input (Green)
3
Open
Closed
Normal operation
All (Green)
4
Closed
Closed
Normal operation
All (Green)
Warning:
If remote ON/OFF is not used, pin 2 and 3 MUST be bridged together!
7.2.9.2 Internal bus (Bus 6 pin / Bus 8 pin)
•
In a la carte system, Internal bus is pre installed and connected in series from
the first shelf to last shelf.
•
Internal bus is comprised of 6 and 8 pole CAN bus cables.
•
If more than one shelf is ordered separately and installed in others cabinet, 6
and 8 pin connector of each shelf should be connected in series with all shelf
using CAN bus cables.
•
The internal bus connectors are sensitive and special caution should be taken
during installation to keep them out of harms way.
Bus Cable
Bus Cable
6 Pin
8 Pin
Installation of Bravo 10 - Shelf
23
- Bravo 10 - 48/230 - User manual - v1.2