7.2.5 DC
Model
MCB per Shelf
Cable, min
Lug
Torque
Bravo 10 - 48/230
160 A
50 mm
2
Insulated Ring
type
5 Nm
Note: The Inner hole diameter of DC lug should be 6 mm (M6), and it is recommended to use only the supplied screws.
7.2.6 AC Input
WARNING !!!
Recommendation of IEC 60364 4. 43
431.3 Disconnection and reconnection of the neutral conductor in multi-phase systems
Where disconnection of the neutral conductor is required, disconnection and reconnection shall be such that the
neutral conductor shall not be disconnected before the line conductors and shall be reconnected at the same
time as or before the line conductors.
WARNING !!!
Input Neutral is required to operate the
Inverter, UPS
In TN-S System no 4 pole input switch or
circuit breaker shall be used. If you have to
use 4 pole protective device, be aware that
the neutral against the ground is floating. The
inverter, UPS will operate without problem
but you may infringe the local regulation.
Model
MCB per Shelf
Cable, min
Connector
Lug
Torque
Bravo 10 - 48/230
40 A
6 mm
2
M6
Insulated Ring
type
5 Nm
Note: Icc value measured as 50 A
rms
per shelf with five modules.
7.2.7 AC Output
Model
MCB per Shelf
Cable, min
Connector
Lug
Torque
Bravo 10 - 48/230
32 A
6 mm
2
M6
Insulated Ring
type
5 Nm
Installation of Bravo 10 - Shelf
21
- Bravo 10 - 48/230 - User manual - v1.2