Operator’s Manual
HPS10IC Pellet Stove
Check for parts online at
www.castlestoves.com
or call 800-345-6007 M-F 8-5 CST
13
PREFERRED PELLET VENT TERMINATION CLEARANCES
• The stove vent must terminate on the outside of the building. Horizontal terminations must extend a minimum of 12” from
the wall. Vertical terminations must protrude a minimum 24” from the roof surface. In addition, all clearances listed below
must be met. SEE FIGURE 7.
• Must have an approved cap (to prevent water from entering) or a 45° downturn with rodent screen.
• If the termination is located on a windy side of the house, we suggest using an approved house shield to prevent soot from
building up on the side of the house.
• A vent must not be located where it will become plugged by snow or other material.
A: A Minimum 4’ clearance below or beside any door or window
that opens. (This clearance may be reduced to 18” if using out-
side air). We recommend the door or window be kept closed
during operation. Minimum 1’ clearance below or beside any
window that does not open.
B: Minimum 1’ clearance above any door or window that opens.
C: Minimum 2’ clearance from any adjacent building.
D: Minimum 7’ clearance above any grade when adjacent to public
walkways.
NOTE: Vent may not terminate in covered walkway or breeze-
way.
X
H
F
E
F
A
G
D
B
A
H
C
E: Minimum 2’ clearance above any grass, plants, or other com-
bustible materials.
F: Minimum 3’ clearance from any forced air intake of any other
appliance.
G: Minimum 2’ clearance below eaves or overhangs.
H: Minimum 1’ clearance horizontally from combustible wall.
X: Must be a minimum of 2’ above the roof.
Figure 7: Vent Termination