background image

EQSER30 

 

Pagina 4 di 10                                                                                                                                                                           Rev. 01 del 06/10/2008 

 
4.3 

Programming and deleting radio codes (only for EQSER30E and EQSER30) 

The PROG button on the control unit is used to store new codes and delete the entire list of codes. 
 

Programming 

 

Power the control unit correctly. 

 

Press the PROG button: the red LED lights up to signal that programming is in progress. 

 

Make a transmission by pressing the transmitter button associated with the enabled channel. 

 

The  code  is  stored.  The  LED  flashes  while  memorising  the  code.  Afterwards,  the  LED  is  lit  with  a  steady  light  to  signal  that  a  new  code  can  be 
entered. 

 

Store all the transmitters by making a transmission with each one. 

 

Afterwards, press the PROG button again to exit the procedure. The LED switches off. Ten seconds after storing the last code, the procedure closes 
automatically. 

 

The codes stay in the memory even in the event of a blackout. 

 
Total deletion of codes  

 

Press and hold down the PROG button until the red LED starts to flash 

 

Press button P1 again within 10 sec. to confirm the deletion. The LED flashes rapidly to confirm the deletion. 

 
4.4 

Learning work times 

The control unit can learn the opening and closure work times. To enter learning mode, the control unit must be in stop-closed status. 

 

Press the programming key once and release it. The LED lights up with a red steady light. 

 

Press the programming key again for approximately 2 seconds until the LED flashes briefly. 

 

Within 10s, press the enabled key of the transmitter or close the OPEN contact to activate the motor opening manoeuvre. The control unit starts to 

measure the opening work time. At the end of the work time, press the key of the transmitter again or the OPEN key. The motor stops in standby. 

 

Press the enabled key of the transmitter or close the OPEN contact to activate the motor closure manoeuvre. The control unit starts to measure the 

closure work time. At the end of the work time, press the key of the transmitter again or the OPEN key. The motor stops in STOP status and the LED 
switches off. The procedure is terminated. 

While making the manoeuvre, the control unit adds 2 seconds to the set manoeuvre times, to ensure the manoeuvres are completed even in the event of slow-
down due to environmental conditions or wear. 
 
4.5 

Selecting the courtesy light or autonomous flashing light  

The output LAMP can operate as a courtesy light or flashing light. 
For the “courtesy light”, the output is active for 1 minute starting from the beginning of each manoeuvre. 
For the “flashing light”, the output activates 2 seconds before the beginning of each manoeuvre (pre-flash) and stays active for the duration of the manoeuvre. 
An autonomous flashing light with 230VAC power supply must be connected. 
 
Insert the jumper CL/WL in position CL to operate with the “courtesy light”. 
Insert the jumper CL/WL in position WL to operate with the “flashing light”. 
 
4.6 

Description of operating modes  

If the STOP contact is open, the control unit accepts no commands via radio or from the terminal board. 
If the STOP contact is closed, the control unit can only carry out manoeuvres according to the following operating modes: 
STEP-BY-STEP MODE 
At each impulse received via radio or on the OPEN contact, the control unit carries out a step in the sequence OPEN-STOP-CLOSE-STOP. 
Reaching one of the limit stops or the elapsing of the work time is equivalent to the STOP situation. 
AUTOMATIC MODE 
At the first impulse received via radio or on the OPEN contact, the control unit carries out the opening manoeuvre. Once the opening manoeuvre is complete, it 
stays in STOP for the duration of the pause time (adjustable via the PAUSE trimmer) then carries out the closure manoeuvre. During the pause, other 
commands via radio or on the OPEN contact have no effect. During the closure manoeuvre, other commands via radio or on the OPEN contact generate a 
new opening and the sequence is repeated. The pause time is adjustable between 3 and 90 seconds via the PAUSE trimmer. 
SEMIAUTOMATIC CLOSURE MODE 
WARNING: in this way the remote control is not usable (unable) 
When the OPEN contact closes, the control unit carries out the opening manoeuvre for the whole time the contact remains closed (or upon reaching the limit 
stop or the work time elapsing) and then goes to STOP condition. 
From the STOP condition, an impulse on the OPEN contact generates the closure manoeuvre. During the closure manoeuvre, a new command on the OPEN 
contact generates a new opening for the entire time the contact is closed. 
SEMIAUTOMATIC OPENING MODE 
WARNING: in this way the remote control is not usable (unable) 
At the first impulse on the OPEN contact, the control unit carries out the opening manoeuvre until reaching the limit stop or the work time elapsing and then 
goes to STOP condition. 
From the STOP condition, when the OPEN contact closes, the control unit carries out the closure manoeuvre for the entire time in which the contact stays 
closed (or upon reaching the limit stop or the work time elapsing) and then goes to STOP condition. 
During the opening manoeuvre, a command on the OPEN contact generates a closure for the entire time the contact is closed (or upon reaching the limit stop 
or the work time elapsing). 
 
4.7 

Photocell operation 

The photocell has a “safety in closure” function.  
During the closure manoeuvre, in modes “STEP-BY-STEP” ,“AUTOMATIC” and “SEMIAUTOMATIC CLOSURE” only, the photocell triggering generates the 
motion inversion until complete reopening. 
During the opening manoeuvre, in all modes, the photocell triggering has no effect. 
In mode “SEMIAUTOMATIC OPENING”, the photocell triggering has no effect. 
In the absence of a photocell, jump terminals PHO and COM on the terminal board.  
In the presence of a photocell, connect the output contact of the photocell to terminals PHO and COM of the control unit so that, with the photocell not 
interrupted, the contact PHO – COM is closed. 

Содержание EQSER30E

Страница 1: ...icevitore radio 433 920 MHz EQSER30E 40 685 MHz EQSER30 Capacit memoria 50 utenti EQSER30E e EQSER30 Sicurezze Fotocellula Ingressi contatto APRE contatto STOP finecorsa apertura finecorsa chiusura Us...

Страница 2: ...l jumper CL WL nella posizione CL per impostare il funzionamento luce di cortesia Inserire il jumper CL WL nella posizione WL per impostare il funzionamento lampeggiante 4 6 Descrizione delle modalit...

Страница 3: ...AC Motor output 230VAC Max 500W Radio receiver 433 920 MHz EQSER30E 40 685 MHz EQSER30 Memory capacity 50 users EQSER30E and EQSER30 Safety devices Photocell Inputs OPEN contact STOP contact opening l...

Страница 4: ...erate with the flashing light 4 6 Description of operating modes If the STOP contact is open the control unit accepts no commands via radio or from the terminal board If the STOP contact is closed the...

Страница 5: ...Hz EQSER30 Capacit m moire 50 utilisateurs EQSER30E et EQSER30 S curit s Photocellule Entr es contact OUVERTURE contact ARRET fin de course en ouverture fin de course en fermeture Sorties Lampe d clai...

Страница 6: ...r s lectionner le fonctionnement lampe d clairage Enfoncer le cavalier CL WL en position WL pour s lectionner le fonctionnement feu clignotant 4 6 Description des modes de fonctionnement Si le contact...

Страница 7: ...33 920 MHz EQSER30E 40 685 MHz EQSER30 Capacidad de memoria 50 usuarios EQSER30E y EQSER30 Seguridades Fotoc lula Entradas Contacto ABRE contacto PARA final de carrera en abertura final de carrera en...

Страница 8: ...nto l mpara de iluminaci n Insertar el puente CL WL en la posici n WL para seleccionar el funcionamiento indicador intermitente 4 6 Descripci n de los modos de funcionamiento Si el contacto STOP est a...

Страница 9: ...otorizzare nonch delle deformazioni che dovessero intervenire nell utilizzo I dispositivi di sicurezza fotocellule coste sensibili stop di emergenza ecc devono essere installati tenendo in considerazi...

Страница 10: ...s radiocommandes et ou tout autre dispositif de commande afin d viter que la porte ou le portail automatis s puissent tre actionn s involontairement En cas de panne ou de mauvais fonctionnement du pro...

Отзывы: