53
<Limit mode 2> Relay Operation Graph when #2 of F51 is set
Weight Stable
Step2
–
Free Fall
Step1
Near Zero
SP1 Output 1
SP2 Output 2
SP3 Output 3
SP4
Output 4
Finish Output 5
Near Zero Output 6
Note.
1. Set value input requirement: Step2– Free Fall > Step1
2. Near zero output is according to the specified range in F57.
3. T1: Refer to F52 (Delay time of weighing Finish relay output)
T2: Refer to F53 (Operation time of weighing Finish relay output)
T5: Refer to F56 (Operation(ON) time of Weighing NG relay output)
4. Relay Output
SP1: ON when the set value of Step1 is reached
SP2: ON when the set value of Step1 – free fall is reached
Finish : On after T1 (set time), ON after T2 (set time)
Lowest Limit NG: Upon weighing finish, ON when lower than the set value of Step2 –
Lowest Limit NG
Upper Limit NG: Upon weighing finish, ON when higher than the set value of Step2 +
Upper Limit NG
Near zero: F57 set value
≥
0 range output
5. SP1,2 ‘s status lamps in the front panel are operated in the same manner as the RELAY output.
T1
T2
T5
T5
Содержание CI-502A
Страница 1: ... 2 ...
Страница 9: ... 10 External Appearance and Dimensions External Appearance CI 502A CI 505A ...
Страница 10: ... 11 Dimensions of the Product CI 502A CI 505A ...
Страница 11: ... 12 Front Panel Descriptions CI 502A CI 505A ...
Страница 27: ... 28 9 th Step Item MovebacktotheWeighingMode ...
Страница 67: ... 68 Weight Data 8 byte a 13 5kg 1 3 5 b 135kg 1 3 5 c 135kg 1 3 5 ...
Страница 74: ... 75 Sealing Method Sealing 1 Sealing the Indicator Sealing the Load Cell Connector ...
Страница 83: ... 84 MEMO ...
Страница 84: ... 85 MEMO ...
Страница 85: ... 86 MEMO ...
Страница 86: ... 87 MEMO ...
Страница 87: ... 88 ...
Страница 88: ... 89 ...