Reference Manual V1.10
Software Versions 3.xx
Page 14
X300-621-110
3.8.3. Outputs
The output drivers for the
instrument are high side drive and are capable of driving up to
400mA each. This configuration allows for the direct connection of the
instrument
outputs to
most types of PLC.
The voltage applied to the
the instrument’s positive power supply terminal (+)appears on the
output lines (Over, Pass and Under) when the outputs are active (eg. to connect to a PLC
c24V to the common terminal). The outputs can then be connected directly to PLC
inputs.
To drive external loads (eg. relays), connect the output line directly to the positive side of the
relay coil. Connect the negative side of the relay coil to COMMON. It is recommended that
fly-back diodes or transient suppressors be fitted across relay coils to limit switching noise.
Figure 11: Instrument Outputs to Drive Relay
Figure 12: Instrument Outputs to Drive PLC