9
Installation of air-inlet grille
The angle of air-inlet grille should be parallel with that of air inlet direction; otherwise it will cause more noise. As shown in
the figure on the right.
Installation of Duct Pipe of Indoor Units:
1. Installation of the air blowing pipe:
With a square blast pipe, the bore shouldn't be less than the sizes of air outlet pipe.
2. Installation of the air return pipe: Connect one side of the air return pipe to the air return port of the indoor units with
rivets. Connect the other side to air return shutter, as shown in Fig.
3.Insulating Supply Ducts: Supply and return air ducts should be insulated.
Selection of fan outlet
Air in
Air in
Correct
Wrong
Grade
1
2
3
4/Standard Esp
5
6
7
8
9
10
11
ESP/Pa
0
40
70
100
120
150
170
190
210
230
250
This machine uses a DC motor. Multiple ESP adjustments are available. The factory default is standard ESP. The ESP &
Silent mode can be set according to the static pressure and the noise levels preferred.
Setting ranges are as follows:
Operation:
40VCW317FQEE wired controller: With the display on, press the Menu key to enter the menu interface. Press Installer
Settings key to enter the interface. Then select Special Settings and enter password: 841226. ESP is the corresponding
static pressure gear number function. When the left and right arrows are flashing, press the Enter key to confirm. When
the left and right arrows are still, press left and right keys to adjust. After adjustment, press Enter to confirm. For more
details on operations with other wired controllers, please refer to the technical manual.
Installation Procedures
Drainpipes
(a) Keep a gradient (1/50-1/100) of the drainpipes and avoid lobing or curving.
(b) When connecting the drainpipe to the equipment, don't apply too much force on one side of the equipment. Meanwhile,
the piping should be positioned as close to the equipment as possible
(c) For the drainpipe, a general purpose hard PVC tube can be purchased at local shops. During the connection, insert
the end of PVC tube into the wash port and fasten it with drainage hose and thread clip. Binding agents shouldn't be
used to connect the wash port and drainage hose.
• Proper Piping
• Improper Piping
hanging bolt
1.5m ~ 2m
heat insulator
gradient of 1/100 or over
air outlet port
avoid lobing
avoid curving
don't put pipe into water
Содержание XCT 7 40VD072H-7S-QEE
Страница 21: ...14 Installation Procedures Address Indication Indication Indication Indication ENGLISH...
Страница 30: ...The manufacturer reserves the right to change any product specifications without notice...
Страница 47: ...14 Procedure di installazione Address Indication Indication Indication Indication ITALIANO...
Страница 56: ...Il produttore si riserva il diritto di modificare qualsiasi specifica del prodotto senza preavviso...
Страница 73: ...14 Proc dures d installation Address Indication Indication Indication Indication FRAN AIS...
Страница 82: ...Le fabricant se r serve le droit de modifier les sp cifications du produit sans pr avis...
Страница 99: ...14 Installationsverfahren Address Indication Indication Indication Indication DEUTSCH...
Страница 108: ...Der Hersteller beh lt sich das Recht vor Produktspezifikationen ohne vorherige Ank ndigung zu ndern...
Страница 125: ...14 Procedimientos de instalaci n Address Indication Indication Indication Indication ESPA OL...
Страница 134: ...El fabricante se reserva el derecho de cambiar cualesquiera especificaciones de producto sin previo aviso...
Страница 151: ...14 Procedimentos de Instala o Address Indication Indication Indication Indication PORTUGU S...
Страница 160: ...O fabricante reserva se o direito de alterar as especifica es do produto sem aviso pr vio...