Troubleshooting
VVT Bypass II Controller
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
38
2
Insert the compressed air straw 1/4" into the controller's
High
connector.
WARNING
The compressed air can MUST be upright. It will damage the flow sensors by producing
ice crystals if the can is on its side.
3
Press the air can's trigger twice for no more than 2 seconds each time.
4
Reconnect tubing to the
High
and
Low
flow sensor tubes.