Wiring inputs and outputs
TruVu™ MPC Controller (
part no. TV-MPCXP1628-NR)
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
34
Outputs
The TV-MPCXP1628-NR's universal outputs can be set as analog or binary on their two DIP switches.
Analog outputs
Outputs set up as analog can be used for:
•
0-10 Vdc devices
•
0-20 mA devices
WARNING
Do not apply voltage to any output whose DIP switch is set to Analog.
If output controls a...
Resistance to ground must be...
0
–
10 Vdc device
500 Ohms minimum
0
–
20 mA device
500 Ohms maximum
NOTE
The device must share the same ground as the controller.
Binary outputs
The outputs have a built-in relay and provide a dry contact so an external voltage source must be wired to one of
the two terminals.
Outputs set up as binary can be used to switch external devices and relays up to 1A, 30 Vac/Vdc.