Addressing the TV-MPCXP1628-NR
TruVu™ MPC Controller (
part no. TV-MPCXP1628-NR)
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
24
9
If the
Broadcast Distribution Table
contains IP addresses that are not in your .bdt file, verify that they are
valid BBMDs and, if so, add them to your .bdt file.
NOTES
○
The BDTs in each BBMD should be identical. Repeat this entire process whenever a BBMD is added.
○
If needed, disable the checkbox next to
Show Broadcast
to limit the amount of scrolling text that is
displayed.
10
Click the
Broadcast Distribution Table
Browse
button and select the .bdt file that you made in step 4.
11
Verify that the appropriate IP address is still in the
IP Address
or
Host Name
field.
12
Click the
Broadcast Distribution Table
Write
button.
13
Click
Read
again to verify that the new .bdt file was written to the router. See example below.
NOTE
If you have a large BDT, you may have to re-size the
BBMD Configuration Tool
window to see the
Broadcast Distribution Table
.